Medical building operating room or surgery, maternity ward, intensive care unit, valuable precision medical equipment rooms, storage, laboratory, film room, attached to the building nursery, kindergarten children's room and children's playground and other children's activities, care facilities for the elderly, should be used with a fire-resistant limit of not less than 2.00h fire partition walls and 1.00h floor with other places or parts of the separation, the wall must be set up doors, windows should be B fire doors, windows, AC option is correct; according to 6.2.1, the stage under the fire separation between places, the following errors ( ). Places or parts of the separation, the wall must be set up doors, windows should be used Class B fire doors, windows, AC option is correct; according to 6.2.1, the lower stage lighting operation room and combustible storage room should be used with a fire-resistant limit of not less than 2.00h fire partitions to separate from the other parts of the fire. Movie projection room, reel room should be used with a fire resistance limit of not less than 1.50h fire partition walls and other parts of the separation, observation holes and projection holes should take fire separation measures, B options are wrong, D options are correct.