The fire safety work of the server room is extremely important, once a fire occurs, it will directly affect the normal operation of the equipment in the building, and cause great losses to personal safety and economic property. In order to prevent fire safety accidents, to ensure that fire safety accidents can be quickly, efficiently, rationally and orderly disposal, especially the development of this plan.
First, the main factors of electrical fires
1, electrical line short-circuit, overload, grounding resistance is too large and other causes of fire.
2, because the equipment in the room for a long time uninterrupted operation or equipment failure caused by fire.
3, static electricity generates fire.
4, lightning and other strong electricity invasion caused the fire.
Second, the disposal process
1, after the discovery of the fire, quickly cut off the power supply, the use of the nearest fire extinguisher to extinguish the fire, and in accordance with the special accident notification mechanism to notify the leadership of the fire to report the specific circumstances.
2, quickly organize the relevant personnel to carry fire apparatus to the scene to extinguish the fire, and listen to the site commanders.
3, such as the fire is more serious, should immediately get in touch with the building fire control, and consult with the treatment measures, if necessary, need to professional fire extinguishing, and quickly ask the leadership to dial 119.
Third, attention
1, once the fire in the room, should follow the principle of: first to ensure that Personnel safety; secondly, to ensure the safety of critical equipment; and then to ensure the safety of general equipment; the fire fighting process should be while fighting the fire, while the alarm.
2, when the fire occurred, the first discoverer to identify the cause of the fire, such as caused by the power supply, should first cut off the power.
Fourth, preventive measures
1, the electrical equipment in the computer room regular inspection. Found that there are problems with the timely maintenance of equipment to eliminate potential safety hazards.
2, every day on a regular basis on the computer room important electrical equipment and electronic equipment ` temperature monitoring, can be found in a timely manner and eliminate hidden dangers.
3, should organize the relevant personnel for fire safety education, learning fire knowledge, learn to use a variety of fire extinguishers correctly, with plans for related fire drills.
Electrical fire emergency plan 2
Article 1 prohibit open flame in the machine room prohibit smoking, all the equipment in the machine room need to be regularly maintained and do inspection records, according to the actual situation of the machine room to clean up the work.
Article network equipment maintenance in the computer room by the network administrator, such as the discovery of machine malfunctions should be timely troubleshooting, in the case of hardware within the scope of the three packages of faults, should be timely to contact the supply company door to door or send the machine to the supply company for repair.
Article 3 The hotel staff must strictly abide by the provisions of the management of the computer room, equipment and system operation, and shall not engage in work unrelated to system management, operation and maintenance, system installation and debugging in the computer room.
Article IV do a good job of fire prevention, rain, humidity, anti-theft work, pay attention to the safety of electricity; machine room. The environment should be checked weekly temperature, humidity, power system, whether to meet the standard requirements related to the machine room.
Article V. The switch and server in the server room are the key equipment for the operation of the hotel, and no one can configure or change the system parameters by themselves.
Article 6 to do a good job of security in the server room, the server's various accounts, passwords strictly confidential.
Article VII should do a good job of backing up data in a timely manner to ensure that when the system fails, the data can be quickly and safely restored. All backup data shall not be changed, and require to do local and off-site backup saved separately.
Article 8 In order to ensure the normal operation of the hotel's network, the daily inspection of the equipment in the server room, mainly focusing on the normal operation of the server and network equipment.
1, the temperature in the server room to regulate, such as indoor temperature is too high, adjust the air conditioning for effective ventilation of the server room.
2, check the switch and firewall and access to the state of the equipment, such as the occurrence of abnormalities, their timely and effective maintenance.
3. Monitoring network operation.
Article IX In addition to the hotel's network administrator, the company's other personnel need to enter the computer room for work, need to be accompanied by the network administrator to enter the computer room.
Article 10 It is strictly prohibited to bring outside personnel or unrelated personnel to enter the computer room, indeed, because of the work required, such as: system troubleshooting and processing, equipment repair and maintenance, system or equipment installation and other access to the computer room, must be accompanied by the network administrator to enter, with the implementation of the project.
Article 11 of the equipment into the server room should be removed before entering the server room packaging to ensure that the environment of the server room clean and safe.
Article 12 It is strictly prohibited to bring flammable, explosive, corrosive and other dangerous items into the server room.
Article 13 The UPS power supply provided in the server room is only allowed to supply power to the host, servers, network and storage and other core equipment, and it is strictly prohibited to install other equipment to increase the UPS power supply load.
Article 14 It is strictly prohibited to cut off the power supply system without authorization, and when power cuts are required for work, the first step should be to make appropriate preparations, approved by the departmental leadership, and then issued to all departments to cut off the power or disconnect the network notification, and then finally can be implemented.
Article XV of the computer room installation of electrical equipment or electrical needs of the project, it must be a professional or equipment provider of the installation engineer to carry out on-site investigation, after confirming that in order to meet or comply with the requirements of the project can be implemented.
Electrical fire emergency plan 3
First, the list of production safety leadership group
Leader:
Members:
Second, the emergency rescue organization
Production Safety Command
1, the general commander: ? Comprehensive organization and mobilization of personnel.
2, deputy commander-in-chief: coordinating the work of the commander-in-chief, directing personnel to fight fires and the evacuation of people and materials, the commander-in-chief is not to perform the duties of the commander-in-chief.
3, fire fighting action group leader: number: 20
4, communication and liaison group leader: number: 2
5, evacuation guide group leader: number: 3
6, safety protection and rescue group leader: number: 3
Third, the procedures and measures to fight the initial fire
< p> 1, in the event of a fire, the fire is not a fire. p> 1, in case of fire, should promptly cut off the power supply, fire source, and the nearest use of fire extinguishers and indoor and outdoor hydrants to fight.2, eliminate flammable and explosive chemicals in the fire area, rescue the injured and valuables.
3, when the fire area is large, the situation is more serious, to withdraw from the scene in a timely manner. 4, when the fire department arrived at the fire scene to cooperate with the fire department to fight the fire.
Fourth, the alarm and police disposal procedures
1, anyone who finds a fire, you must immediately notify the surrounding personnel, report the fire alarm: you can shout "fire", but also call "119" to the fire brigade. "to the fire department alarm.
2, the fire watchman received the fire alarm signal, should immediately confirm. When the fire is confirmed, immediately notify the unit personnel rushed to the scene, and report to the production safety command. According to the deployment of the production safety command, notify the relevant personnel to take action. When dialing "119" to call the police, you should say: Zugezhuang Dongkou Qiaoben Electrical Appliance Factory, and state the alarm number and name. After the alarm should be sent to the door junction to meet the fire department into the fire.
Fifth, the emergency evacuation of the organization procedures and measures
1, the safety evacuation door all open, clean up, evacuate the safety exit, the channel in the chores, to ensure that the evacuation of the safety of the exit open, the organization of the evacuation of the people present in the vicinity of the safety exit.
2, stabilize the fire escape personnel emotions, guide everyone to use the correct escape method. Guide everyone to do a safe evacuation, to prevent the occurrence of crowded, step on the situation
3, will be the fire in the timely evacuation of the vehicle, pay attention to traffic diversion.
Six, fire emergency rescue plan
1, in order to effectively and quickly fight fires, evacuate people, minimize fire hazards, according to the "public **** entertainment fire safety management system" and other laws and regulations, the development of this plan.
2, in the event of a fire, according to the operating procedures of this plan, the full launch of the initial fire fighting, alarm, evacuation and safety protection.
3, found in the market smoke or received a fire report, the commander-in-chief, deputy commander-in-chief to lead the fire-fighting action group to implement the emergency fighting, in the early stages of the fire or the smaller use of dry-powder fire extinguishers to fight. If it is determined that the fire can not be extinguished with dry powder fire extinguishers, according to the instructions to immediately start the fire hydrant to extinguish the fire, and immediately call the police. (Alarm phone: 119)
4, fire accidents, 8:00 am to 5:30 pm during the day by the head of the evacuation action group to lead the evacuation team members are responsible for the evacuation of the site of the vehicle and personnel in a timely manner for the fire trucks to open up the road, guide the fire trucks to enter the fire scene. In different locations by the team leader maneuvering to master the command.
5, the fire fighting process, such as the occurrence of casualties, during the day at 8:00 am to 5:30 pm by the head of the safety protection team and members of the rescue team is responsible for reporting to the 120 for first aid, and the injured personnel to quickly take away from the scene of the fire.
6, fire accidents at night, by the security team to implement emergency rescue, while immediately notify the groups and the presence of personnel to urgently arrive at the scene of the fire, in accordance with the operating procedures of the plan and the emergency rescue organization to carry out the rescue of the personnel division of labor.
VII, safety protection procedures and measures
1, demarcate the cordon, determine the scope of the realm. Closely protect the scene, strictly prevent unrelated personnel from entering the fire, to prevent bad people to take the opportunity to carry out destruction and theft.
2, to assist the medical staff to rescue the fire injured casualties.
3, after the fire is extinguished, protect the scene and wait for the arrival of fire investigators. As soon as possible to identify the cause of the fire.
Electrical fire emergency plan 4
First, the prevention of electrocution, judgment and treatment
1, prevention, judgment
1) electrical equipment overhaul must be carried out by more than two people;
2) electrical equipment to be overhauled to first disconnect the power. Hang warning signs to determine the absence of electricity, hang the grounding wire, and then construction;
3) electric operation, overhaul of electrical equipment should be insulated to protect;
4) the above work should be carried out in strict accordance with the operating procedures of electrical appliances.
2, processing
In the event of an electric shock accident, should first cut off the power supply of electric shock. If the neighborhood can not cut off the power supply, with an insulated rod or dry, non-transferable poles, wood, etc. to make the electrocuted person and the power supply or equipment to disengage. And the electrocuted person to take emergency rescue measures.
Second, electrical equipment fire accident prevention, judgment, treatment
1, prevention, judgment
The electrical equipment belonging to the regular inspection. Motors, switches, lines and electricity and other equipment in the operation process whether overheating. Whether the joints are loose, or other abnormal phenomena. For abnormal equipment timely maintenance.
2, processing
Once the fire, first of all, to cut off the power supply of the equipment or lines on fire. (Where permitted, it is best to cut off the power supply of neighboring equipment). Then use a dry powder fire extinguisher against the fire parts to extinguish. And pay attention to the neighboring electrified parts. Pay attention to safety. Strictly prohibit the use of water to extinguish the fire.
Third, emergency tripping accident prevention, judgment, treatment
1, prevention, judgment
1) not put into use of electrical equipment should be regularly inspected, and test run. Not only to ensure that the equipment is good standby condition, but also on the electrical equipment itself moisture evaporation, protection of insulation, to prevent rust.
2) for running equipment, before running to disk, and according to its rated power operation.
3) Running equipment to regularly check its operating current, should not exceed its rated current value.
4) Electrical equipment before the line is put into use, the insulation should be checked to ensure that the insulation meets the requirements to be activated.
5) Electrical switches are regularly calibrated for thermal loads.
2, processing
Electrical equipment tripped, should not be immediately restored to power. To find out the reason, and then according to the steps of power supply to close the gate operation.
Electrical fire emergency plan 5
In order to make the information room fire accidents, on-duty personnel can calmly and orderly disposal of the incident, specially formulated this plan, please members of the study carefully, familiar with the emergency disposal procedures, improve the emergency response ability of the whole staff, once an emergency occurs, to do their best to ensure the personal safety of the staff and to reduce the loss.
The causes of fire are generally careless management of open flames; improper management and use of electrical equipment; arson and other reasons.
Prepared for a: when smell the burning smell
The duty officer found that the information room smoke phenomenon or smell the burning smell, may be somewhere in the negative combustion is in the stage of fire or power overload caused by heat, easy to cause a fire, the duty officer to immediately find out the cause and location, for different situations, take the fire quickly extinguished or shut down the power main switch, the heat caused by the overload, easy to cause a fire. The staff on duty should immediately identify the cause and location of the fire, and depending on the situation, take measures to quickly extinguish the fire or turn off the main switch of the power supply, isolate the flammable materials near the fire source, and close the windows to eliminate the hidden fire hazards and prevent the fire. The fire is not only a great way to prevent the fire from spreading, but also a great way to prevent the fire from rekindling, and not to leave the scene and hide the accident.
Prepared for two: on duty found fire or smoke
Due to the hidden source of ignition or other unexpected reasons for failure to detect and eliminate fire hazards in a timely manner, brewing open fire and smoke, combustion area is not large, it is the incipient stage of the fire, the staff on duty to find a fire or smoke, do not be panic, calm, decisive, together with other staff on duty to divide the fire into two parts, the first part of the fire, the second part of the fire, the second part of the fire, the third part of the fire, the second part of the fire, the third part of the fire, the second part of the fire, the third part of the fire. When the fire has been unable to control the disposal method:
One is to designate a person to immediately pull the "119" fire alarm telephone alarm and report to the higher security department, and to the department and around the people and the masses shouting alarm;
Two is to Organize the unit, the department present. Personnel put into fighting work in an orderly manner, make full use of fire hydrants, fire extinguishers, buckets and other equipment to extinguish the fire, can not passively wait for the arrival of the fire department, and miss a good opportunity to extinguish the fire, and strive to extinguish the fire or control the spread of the fire, and can not only focus on personal safety and escape from the fire;
Third, shouting to request the support of the neighboring units and the masses;
Fourth, in the organization of the extinction of the fire at the same time, we must immediately organize the people Evacuation and transfer of goods, especially Chang flammable, explosive substances and easy to be threatened by the tongue of the cash, important credentials to be transferred to a safe place in a timely manner, and send personnel to guard, to ensure safety;
Fifth, the fire should pay attention to the protection of the scene after the fire, to maintain order, in order to facilitate the fire department to investigate and analyze the cause of the fire.
Notes:
Alarm personnel alarm to the fire department to tell the fire location, units, the type of fire and fire size, alarm that after the street or intersection to meet, guide the arrival of fire vehicles; fighting personnel in the arrival of firefighters, immediately to the fire commanders to tell what kind of fire stored in the fire scene. Materials and valuables, whether there are explosives, poisonous substances in the fire, and to assist the fire department to maintain the order of the scene. When fighting the fire by yourself, you should pay attention to observe the fire and the environment, to prevent being surrounded by fire, smoke poisoning, falling objects, etc., in order to ensure their own safety in the case of fighting the fire.
Electrical fire emergency plan6Article 1 server room emergencies, including network equipment or server failure, natural disasters (water, fire, electricity, etc.) caused by physical damage, human error caused by the security incident and so on. Preventive measures for emergencies are as follows: establish a safe, reliable, stable operation of the computer room environment, fire, theft, lightning, water, static electricity, dust; establish a backup power supply system; strengthen the awareness of fire and theft.
Article II of the machine room leakage emergency plan is as follows:
First, the occurrence of machine room leakage, the first witness should immediately notify the management of the machine room.
Second, if the air conditioning system leakage of water, the server room managers should immediately arrange to stop the faulty air conditioning, remove the water in the server room, and promptly contact the equipment supplier to deal with, if necessary, temporary use of electric fans on the servers to cool down.
Third, if the wall or window leakage, the server room management should immediately take effective measures to ensure the safety of the server room, and at the same time arrange to notify the engineers to remove the water in a timely manner, maintenance of the wall or window, to eliminate the leakage of water hidden trouble.
Article III of the machine room fire emergency plan is as follows:
First, improve the environment of the machine room to ensure that the machine room to place fire extinguishers; prohibit the carrying of flammable and explosive substances into the machine room.
Second, the management of the server room should be familiar with the internal fire safety operations and rules of the server room, understand the operating principles of fire fighting equipment, master the steps, measures and essentials of fire emergency response, know how to extinguish the fire, and will put out the incipient source of fire.
Third, in the event of a fire, quickly cut off the power supply to the server room to avoid the spread of the disaster, and quickly contact the security department to immediately report the fire alarm if necessary.
Article IV of the machine room power outage contingency plan is as follows:
First, upon receipt of the notice of the power outage, should be timely through the office system, telephone and other relevant information released, deployed to respond to specific measures, required to stop the business before the power outage, save the data.
Second, the computer room managers check the status of the UPS power supply on a daily basis to ensure that in the event of an unexpected power outage, the UPS power supply can automatically supply servers to work normally for more than 15 minutes to ensure that the data of the employee's work in a timely manner to save.
Article V Emergency Plan for Communication Network Failure is as follows:
I. After the occurrence of communication line interruption, abnormal flow and other failures, the employee or department head who found the situation should notify the network administrator in a timely manner.
Second, the network administrator understands the situation, quickly organize the detection of faulty areas, and make relevant troubleshooting, and gradually restore the faulty area and the server's network connection, restore the communication network to ensure normal operation.
Article VI server failure emergency plan is as follows:
First, the server room managers check the status of each server in the server room every day.
ii. Regular backup of data server data. And copy the backup data to a mobile device. Servers with serious hardware failure to enable backup servers to ensure normal operation.
Electrical fire emergency plan 7
In order to conscientiously implement the "State Council on the provisions of administrative responsibility for large-scale security incidents", and actively improve the company's key critical parts of the emergency response capacity of large-scale security incidents, and strive to reduce the loss of various types of large-scale security accidents, to eliminate the potential fire accidents, and to protect the company's property and the safety of the staff's lives, the development of this plan.
This plan is formulated for the fire in the communication room of our company.
Mobile communications room fire fighting process is as follows:
(a) the duty officer found the room fire (including the monitoring center staff) to immediately go to the scene to check.
(b) If individual circuit boards are on fire, the fire circuit boards should be pulled out, and the fire should be extinguished with 1211 or carbon dioxide fire extinguishers.
(C) a cabinet several circuit boards and cables on fire, should immediately pull out the fire circuit boards, with 1211 or carbon dioxide fire extinguishers spray extinguishing agent to extinguish the fire.
(d) If the rack cabinet in the server room is on fire, the duty officer is unable to extinguish the fire, the monitoring center should cut off the rack cabinet power supply or floor power supply, turn off the air conditioning, prohibit the opening of windows, and promptly report to the company's leading group of production safety management.
(e) the company's leading group of production safety management to direct the organ of the volunteer fire department members to extinguish the fire, the organization on duty to immediately evacuate the scene, close the doors and windows, press the regional automatic fire button to extinguish the fire, and at the same time, call 119 alarm, call for help, report to the company's competent leadership or security duty room, the monitoring room to broadcast the fire alarm.
(F) in the fire department arrived, should actively cooperate with a brief description of the location of the fire, the fire situation and the remedial measures taken.
(7) with 1211 or carbon dioxide fire extinguishers to spray extinguishing agent can put out the fire, should cooperate with the fire department to protect the scene and eliminate hidden dangers, to prevent the fire again.
(h) with 1211 or carbon dioxide fire extinguishers can not put out the fire, in order to prevent smoke caused by personnel poisoning, should organize the orderly evacuation of personnel, the use of appropriate fire-fighting equipment, as soon as possible to extinguish the fire.
(ix) should protect the scene, in accordance with the accident investigation and treatment methods.
(J) fire alarm telephone: 119
This plan should pay attention to special matters
1, when the fire situation, to deal with and ensure personal safety at the same time, according to the importance of the equipment to carry out the corresponding rescue measures to ensure that the important equipment, in particular, through the phone, as well as the corresponding data uploaded with the Jibei, North China, to ensure that the channel is open.
2, after the rescue of the main equipment, in the secondary equipment repair, after the accident is completed, the corresponding experiments to ensure the operation of the equipment, and equipment feasibility analysis.