The following statement about medical buildings is wrong ( ).

Answer: A, E

According to 5.4.5 of the Building Design Fire Prevention Code GB 50016-2014 (2018 edition), the inpatient part of hospitals and sanatoriums should not be set underground or semi-underground, and when they are set up in a three-level fire-resistance-rated building, they should be arranged on the first or second floor; when they are set up in a four-level fire-resistance-rated building, they should be arranged on the The first floor; hospitals and nursing homes ward building adjacent to the nursing unit should be used between the fire-resistant limit of not less than 2.00h fire partition wall separation, partition wall should be used on the door of the fire door B, set in the aisle fire door should be used to open the fire door, A option is wrong, BD option is correct; according to 6.2.2, the operating room or operating department, maternity wards, intensive care unit, valuable and precise medical equipment rooms should be used to protect the medical equipment, the fire-resistant limit of not less than 2.00h. Fire resistance limit of not less than 2.00h fire partition walls and 1.00h floor and other places or parts of the separation, the wall must be set up doors, windows should be used B fire doors, windows, C option is correct; according to 5.5.24, high-level ward building should be set up in the second floor and above the ward floors and clean surgical refuge, E option is not more than 24m belongs to the multi-storey public **** building, E option is wrong. The answer to this question AE.