A temporary fire, welding and cutting operations safety management regulations
In order to regulate the scope of the building to engage in temporary fire, welding and cutting operations of units or individuals, according to the People's Republic of China *** and the State of the building fire management rules and the provincial and municipal fire departments, the relevant provisions of the regulations, the provisions of the special formulation of this.
(a) Application
The units or individuals who need to carry out temporary fire, welding and cutting operations within the scope of the building must submit a written application for fire to the management company in advance, which specifies the time of the fire operation, the scope, the content and the name of the operator, and promises to comply with all the provisions of the building, and also submits a copy of the operator's valid operating certificate.
The management company receives the application for approval within two working days. If deemed necessary in the process of approving the application, the management company may request the applicant to submit the original operator's operating certificate and relevant approvals from the fire department for inspection.
(2) graded approval management
Based on the degree of danger of fire, the approval of fire management is divided into three levels:
1. The first level of fire shall be used by the fire department fire prevention responsible person in conjunction with the Ministry of Engineering, the Security Department to carefully inspect the construction site, to determine a reliable fire prevention measures, fill out the first level of application form for fire (a major fire project to write a memo on the topic), by the Management Company After signing and approving by the chief fire prevention officer, it will be reported to the local public security fire prevention supervisory department for approval, and only after confirming that the measures are reliable and have been implemented one by one after the on-site inspection will the fire be approved.
2. The second and third level of fire must be used by the fire department fire prevention officer to develop fire safety measures, fill out the fire application form, reported to the management company's chief fire prevention officer for approval, the Engineering Department, the Security Department on-site inspection and supervision.
3. Welding and cutting (referred to as welding and cutting) is an open flame operation. The public security fire management department stipulates that personnel engaged in welding operations must hold a welder's license issued by the local department after training before taking up welding.
(C) the fire operation of the "eight not", "four to" and "a clear"
1. fire before "eight not "
Fire prevention and fire fighting measures are not implemented not to start a fire.
No fire around the flammable debris is not removed.
No fire without safety measures for nearby flammable structures that are difficult to move.
Where the containers and pipes have been filled with flammable liquids such as oil, do not start the fire without washing and cleaning and removing the residual oil.
Where the gas has been filled with thermal expansion of containers and piping explosion risk will not be ignited.
Where there are flammable and explosive substances stored in rooms, warehouses and places, without removing the flammable and explosive hazards of the fire. No fire will be started when welding or starting welding and cutting operations at a high altitude without the combustible items below being cleaned up or without protective measures being taken.
No fire is started without appropriate fire extinguishing equipment.
2. fire in the "four to"
Before starting a fire to designate the person in charge of site safety.
The person in charge of on-site safety and fire personnel must always pay attention to the fire situation, found the first signs of insecurity, to immediately stop the fire.
When a fire or explosion occurs, it must be put out in time.
The fire personnel should strictly implement the safety regulations.
3. After the fire, "a clear"
Fire personnel and the person responsible for on-site safety in the fire, should be thoroughly cleaned up the scene of the fire, to ensure that the fire is completely extinguished, stay at the scene for 15-30 minutes before leaving the scene.
(4) Violation of the regulations
The management company has the right to take the following measures depending on the severity of the situation if the unit or individual who carries out temporary fire, welding and cutting operations within the building violates the regulations:
1. rectify the situation within a certain period of time;
2. order to stop the fire operation immediately;
3. hand over to the fire control department for processing.
Two, the renovation of the construction site fire safety regulations
In order to strengthen the renovation of the construction site fire management, to ensure that the renovation of the construction site and the building users of personal and property safety, we have formulated this fire safety regulations.
1. The construction site shall be renovated according to the actual area and the use of materials equipped with a certain number of 2kg or more fire extinguishers. Equipped with the standard: 100m2 below neem 2-3; 100m2 above 3-4; half layer 5-6; full layer 8-10.
2. Construction site is strictly prohibited smoking and the use of open flame burning debris, bending hose, etc..
3. Flammable, explosive, corrosive, toxic and other dangerous substances brought into the building.
4. Organic solvents, paints and other organic solvents required for the renovation project are only allowed to be brought into the day of the required amount of decoration, and taken away on the day of departure, and shall not be stored or stacked in the building.
5. Strictly abide by the provisions of safe use of electricity, no indiscriminate connection of wires or overloading of electricity.
6. Indoor wiring shall use insulated wires and wear hard plastic pipes or steel pipes for open and dark laying, the insulation strength of the insulated wires shall meet the requirements of the power supply voltage, and the insulated wires with rated voltage of 550v shall be used in case of 380v power supply voltage, and the insulated wires with rated voltage of 250v shall be used in case of 220v power supply voltage.
7. Indoor decoration shall be strictly in accordance with the fire safety requirements, the use of non-combustible or flame retardant fireproof materials, shall not use flammable materials.
8. The unit of open-flame welding, welding and fire operations before the management company must first apply to the Ministry of Engineering, in strict accordance with the temporary fire welding and cutting operations safety management regulations.
9. Without the approval of the declaration, unauthorized alterations to touch the smoke detectors, sprinkler heads, emergency broadcasting speakers and fire hydrants and other fire equipment.
10. Indoor decoration intervals must comply with fire safety regulations, such as intervals between the roof, intervals without smoke sprinkler must be added.
11. Decoration and construction can block the fire facilities, evacuation signs and exits, and shall not prevent the normal use of fire facilities and evacuation aisles.
12. In order to avoid the construction site dust caused by the smoke sensor alarm, before the daily construction of the security department agreed to use a plastic bag to wrap the smoke detector, after the end of the daily construction of the wrapping must be removed, to restore the normal working condition of the smoke detector.
13. Before leaving the site at the end of daily construction, the security department shall notify the foreman on duty to the site for indoor fire safety inspection to confirm that there is no security risk before locking the door to leave.
Three, the fire fighting system
In order to strengthen the fire fighting management, to ensure the safety of life and property of the users of the building, according to the People's Republic of China *** and the country's fire fighting law workbook, the development of this system.
(A) the establishment of fire safety committee
According to the Chinese people *** and the provisions of the State Fire Services Act, combined with the actual situation of the building, the establishment of the Fire Safety Committee, the general manager of the General Manager as the general fire prevention, the heads of the departments responsible for fire prevention, engineers and technicians are responsible for the maintenance and management of fire protection facilities to the security department as the main body of the establishment of the volunteer fire department.
1. Duties of the general manager of the building fire prevention
(1) leading fire safety organizations, implementation of fire laws.
(2) Organize the formulation of various rules and regulations of fire fighting.
(3) Organization, layout, inspection, summarize the fire work, and regularly to the local public security, fire supervision report on fire work.
(4) Organization of fire safety inspection, rectification of fire hazards.
(5) fire publicity and education for employees.
(6) Organize and lead the voluntary fire department to carry out fire fighting work.
(7) Organize the management of fire fighting facilities and equipment.
(8) Organize the development of evacuation plans in emergency situations.
(9) Organize to fight the initial fire and guide the safe evacuation.
(10) investigation of fire accidents, to assist the public security fire safety supervision organs to investigate the cause of the fire.
2. Duties of the person responsible for fire prevention in each department
(1) To be the staff of the person in charge of fire prevention in the management company, and to cooperate with the chief fire prevention officer in carrying out and executing the fire laws.
(2) According to the instructions of the chief fire prevention officer, organize fire drills.
(3) Establishing fire prevention files.
(4) Under the direction of the Chief Fire Officer, conducts fire prevention campaigns and inspects and supervises the rectification of fire hazards.
(5) Responsible for fire prevention inspections.
(6) Supervise the implementation of fire regulations.
3. The duties of the responsible person for fire prevention in each shift
(1) the responsible person for fire prevention in each shift is responsible for the next level up, so that "whoever is in charge, whoever is responsible for it", and the fire fighting equipment, fire fighting equipment and facilities to implement the management of the layers of contracting.
(2) Organize regular fire knowledge learning and fire fighting business training for employees.
(3) Daily inspection of fire fighting facilities and equipment in their own jurisdiction.
(4) Daily check whether the location, number and quantity of the equipment are in line with each other, and whether there is any expiration date, damage and loss, make records and report to the Security Department in time.
(5) Require employees to do a good job of cleaning fire extinguishing equipment, keep the appearance of clean and beautiful, neatly arranged.
(6) Teach employees to learn to use general fire extinguishing equipment and fire alarm handling skills, to do "a fire, two rescue, three evacuation, four protection.
(7) Check whether the fire escape channel is smooth, whether the fire facilities are blocked or occupied, and promptly deal with or report to the Security Department.
(8) with the Security Department to do a good job in all fire prevention.
4. Responsible for the maintenance and management of fire protection facilities, engineering technicians
(1) to ensure that the fire water supply system, hydrants and other equipment is complete.
(2) Ensure that the automatic fire alarm system, automatic fire extinguishing system is complete.
(3) Ensure that the smoke and temperature detectors, water sprinkler nozzles, fire doors, smoke doors, fire shutters, smoke evacuation facilities, fire hoses and water hoses, evacuation signs and indicators and other fire facilities are complete.
(4) Regular maintenance and repair of building fire equipment and facilities.
5. Volunteer Fire Brigade
(1) Rapid Action Group: composed of the duty supervisor of the Security Department, the system engineer of the Engineering Department, the manager of the Management Department, the duty security guards of the department and the duty staff of the Engineering Department, and the male employees of the Management Department and the Administration and Personnel Department. Rapid action group found that the fire, should be carried out in the early stages of fire fighting, to prevent the spread of fire. Can not control the fire, should be implemented to fight the fire program.
(2) rescue and evacuation group: composed of secretaries of departments, clerks and employees of the Ministry of Finance, is responsible for rescuing the injured and important documents and materials and evacuate the building personnel.
(3) defense group: composed of some security guards from the security department. When the fire occurs, is responsible for guarding the important parts of the building and guarding the passageway, to prevent outsiders from entering the building, and lead the firefighters to the scene of the fire.
(4) Command Department (group): by the general manager, deputy general manager, chief engineer, security department manager, manager of the management department, responsible for the fire scene fire command work.
I. Regular Fire Safety Inspection System
(1) Regular Fire Safety Inspection System
In order to standardize the fire fighting work of the building and to check and prevent the fire hazards, the following system is formulated:
1. Fire Safety Inspection of the Public **** Areas and Public **** Facilities
(1) At the end of each month and before the festivals, the fire safety inspections are carried out on the various floors of the building, including the public **** areas, public **** facilities and the fire safety inspection of the building. area, public **** facilities for safety inspection.
(2) The inspection is organized by the company's chief fire prevention officer, with the participation of the heads of engineering, security and management.
(3) The inspection items are whether the fire extinguishing equipment and hydrant facilities equipped on each floor are complete and effective.
(4) Check whether the facilities and equipments such as electric switches and appliances in the power distribution room, fan room, pantry and top floor elevator machine room on each floor are in compliance with the fire safety regulations and whether the door locks are intact.
(5) Check whether the corridors, elevator halls, fire escape is smooth, fire escape door, smoke detectors, lights are normal.
2. Fire Safety Inspection in Company Rooms on Each Floor
(1) Check whether there are any matters violating fire safety regulations in each company room.
(2) Check that electrical appliances used in company rooms comply with safety regulations.
(3) Whether the company rooms are equipped with a certain number of fire extinguishers as required.
3. Fire Safety Inspection in Logistics Area
(1) Check whether each fire hydrant and fire extinguisher on the equipment floor is in good condition.
(2) Check whether the facilities and equipments of each machine room and electric room are functioning normally, and whether the fire extinguishing equipments equipped in the machine room and electric room are in good condition.
(3) Check whether the corridors, fire escape routes are smooth, indicator lights and smoke alarm system is normal.
4. If the inspection finds any variation of various facilities and equipments in the building, or any other problems violating the fire safety regulations, the cause should be identified immediately and dealt with in time. Can not be immediately resolved, the management company issued a rectification notice, deadline for rectification.
(II) Related Records
Shift Level Fire Safety Inspection Form (Table 3-11)
Table 3-11 Shift Level Fire Safety Inspection Form
Item
Name Time Star
Term
Found Hidden Disease Situation Rectification Situation Person in Charge Signature
Month
Shift Inspection I
Two
Three
Three
Four
Five
Six
Day
Departmental Divisions
Intentions
Explanations 1. Three-tier fire prevention inspections, i.e., the shift (team) leader and employees every day before and after the shift on the post, the lot of the self-check; by the Department (Division) fire prevention officer responsible for weekly Check once a week by the Department (Division) of the person responsible for fire prevention by the team leader or lot fire prevention registration signature, reported to the Ministry of Security once a week; fire prevention responsibility of the ministries of the organization of the person responsible for the joint inspection of the relevant person in charge once a month.
2. Hidden dangers found should be immediately rectified, difficult to rectify the report to the higher departments responsible for fire prevention
3. Inspection content: should be based on the characteristics of the post, focusing on cutting off the power supply, clean up flammable debris, check whether to leave behind cigarette butts or other hidden dangers, etc.
II. "prevention-oriented, prevention and elimination of combining" fire policy, the development of this system.
1. The management company's fire knowledge training for employees is no less than two times a year.
2. The management company's fire knowledge training for new employees, the training rate should reach 100%.
3. The training for employees includes the following:
(1) Learning the theoretical knowledge of fire fighting.
(2) familiar with the use of commonly used fire extinguishing equipment.
(3) Conducting comprehensive fire drills.
4. The security guards of the Security Department, employees of key positions, foremen and employees of foremen and above positions must participate in the fire fighting knowledge training organized by the Municipal Fire Fighting Association, and the training cost shall be paid by the Company. Employees who receive training must serve in the Company for more than 1 year, and those who have served for less than 1 year must return the training fee.
5. The Management Company will conduct fire prevention education training for users at least twice a year. The contents include:
(1) the regulations of the building fire prevention work.
(2) the use of portable fire extinguishers.
(3) the location of the fire emergency channel and the evacuation method in case of emergency.
Three, fire extinguishers management regulations
1. Fire extinguishers are one of the building's firefighting equipment, used in emergencies and fire status.
2. The fire center is responsible for the management of fire extinguishers, including procurement, acceptance and purchase, inflation plan.
3. Employees are not allowed to move, remove or use stored fire extinguishers in non-emergency situations.
4. After the purchase of fire extinguishers, the fire center is responsible for spraying "** Building" logo and number on the bottle of fire extinguishers, and affixing a label indicating the date of purchase or inflation.
5. In the fire inspection in the middle of each month, the fire extinguishers should be inspected and replaced in a timely manner to replace failed or damaged fire extinguishers, and the expiration date should be indicated on the label of the bottle.
Four, the fire center code of conduct
1. Strictly prohibit smoking, eating and drinking, chatting, sleeping, loud noise and other obstacles to work in the fire center.
2. Improve the fire center environment, equipment health, maintain a clean working environment.
3. Ensure that the special line alarm phone smooth, non-emergency may not use the alarm phone; emergency use of the special line alarm, speech should be simple, clear.
4. Without permission, it is strictly prohibited for unrelated personnel to enter the fire center.
5. The staff of the fire center should abide by the rules and regulations of the building and the security department, be dedicated to their work, and strive to improve their business level; strengthen the exercise to ensure that the physical quality is in a good state of readiness.
V. Fire Drill Procedures
(1) Purpose of the drill
Enhancement of the fire awareness of the staff and the building's personnel of various companies, improve the organization of the fire fighting work and the ability to deal with the fire, and better understanding of the building's fire prevention system and the building's fire escape paths to improve the ability of self-rescue.
(2) Frequency of fire drills
The fire drills of the building are conducted once a year in principle, and the number of drills can be increased with the approval of the person in charge of fire prevention under special circumstances.
(3) Members participating in fire drills
1. The person responsible for fire prevention of the management company and the company leaders.
2. Managers of each department.
3. Volunteer firefighters from each department.
4. The person in charge of fire prevention and staff of each company in the building.
(4) Organization of the drill
The organization of the building fire drill is the specific responsibility of the security department of the management company, with the cooperation of other departments of the management company. Fire drill preparation steps are as follows:
1. Security Department to develop a fire drill program and report to the company's total responsibility for fire prevention approved.
2. Security Department in the two weeks before the fire drill on the existing security guards fire training, exercise the team's endurance and will, in order to achieve the purpose of preparation.
3. Please fire equipment professional salesman on-site guidance, so that all members of the team can master the performance of various equipment and the use of methods.
4. Before the exercise, the management company organized a fire facilities and equipment inspection to ensure that the building's existing fire equipment for normal use.
5. management company to determine the date and time of the exercise, a week in advance to send a letter to notify the building units, and require each unit to provide a list of participants in the exercise.
(E) fire drill process
1. Alarm procedures (security department responsible)
(1) fire alarm, the first fire alarm location reported to the fire monitoring center, the fire center on duty to immediately notify the security guards or the relevant personnel on duty to the scene to confirm that at the same time will monitor the camera in the fire floor for monitoring.
(2) After confirming that the fire alarm is true, immediately notify the manager of the security department or the person in charge of the fire center, according to the plan to quickly call the volunteer firefighters from various departments to the fire scene as soon as possible.
(3) The general manager directs the personnel on the scene to extinguish the fire and save people.
(4) According to the general manager's order, the fire center notifies the users who need to be evacuated by emergency broadcast or presses the alarm.
2. Evacuation Rescue (Management Department is responsible)
(1) Responsible for guiding the evacuation of people to the safety zone, escorting the mobility impaired people to evacuate the danger, and then checking whether there are people left in the burning room; placing the people who have been evacuated from the burning floor, and pacifying and stabilizing their emotions.
(2) Evacuation order. First from the fire room, and then from the fire on the floor above the start, pacify the fire below the floor does not need to evacuate the user, so that they do not run around.
(3) guide self-help. Organize staff to guide users along the fire escape ladder rushed through the smoke down the stairs. Sent to lead the people who can not be evacuated from the scheduled fire escape ladder upwind on the rooftop to wait for rescue, and the organization of water gun spray cover.
3. Organization of fire extinguishing (security department and volunteer firefighters are responsible for)
(1) start the fire pump, ready to fire above the fire layer of each layer of the amount of fire water, laying water belt ready to extinguish the fire.
(2) Close the fire doors of the fire partition.
(3) Carry fire-fighting tools to the adjacent rooms of the fire room and the upper and lower floors of the room access to find out whether there is a possibility of fire spreading, and extinguish the spreading flames in a timely manner.
(4) For different combustion using different fire extinguishing methods.
4. Security alert (Security Department is responsible for)
(1) building perimeter alert task is to eliminate barricades, guide vehicles away from the scene, advise pedestrians and unrelated persons to evacuate the scene, maintain order in the building perimeter.
(2) the first floor of the building entrances and exits vigilance task is not allowed to enter the building, guide the evacuees to leave the building, look after the objects evacuated from the fire floor.
(3) the fire layer of the next layer of vigilance task is to prevent guests from entering the fire layer, to prevent people from taking advantage of the fire to move, to protect the fire equipment and equipment, and to guide the evacuees to the next layer of orderly evacuation.
5. medical rescue (Personnel Department, Finance Department is responsible for)
Some of the personnel to form a medical rescue team, equipped with the required first-aid medicines and equipment, set up a temporary rescue station. The rest of the personnel to protect or transfer important information and books of accounts of their respective departments.
(F) summarize the effect of fire drills
After each fire drill, the Security Department shall summarize in writing the effect of the drill and the lessons learned; the Department of Management is responsible for collecting and summarizing the feedback of the users of the building on the fire drill; the two summaries are submitted to the building's fire prevention of the total responsibility for the review of the archives.
Nine, fire alarm signal processing procedures
1. fire monitoring center on-duty security guards receive fire alarm signals or telephone alarms:
(1) use the intercom to notify the security guards or administrators patrolling the building to the scene immediately to verify;
(2) instantly to the supervisor on duty to report to the police, the location of the alarm;
(3) will be the monitoring lens set to the alarm floor monitoring, and the situation (3) Set the monitoring lens to monitor the alarm floor and report the situation to the supervisor on duty in time.
2. After receiving the call from the on-duty security guard of the fire monitoring center, the security guard or administrator will arrive at the alarm location as fast as possible to verify the situation and follow the following rules:
(1) If the alarm location is in the public *** place, enter the alarm location directly to check.
(2) The alarm location is in an office building unit, ring the doorbell first, briefly explain the reason to the user and then enter the alarm location to check.
(3) The alarm location is in the shopping mall, with the mall management personnel to enter the alarm location to check.
(4) If the alarm location is in a parking lot, enter the alarm location with the parking lot manager to check.
(5) alarm location in the office building unit and locked, immediately report to the supervisor on duty, and stay on watch, waiting for the supervisor on duty to decide whether to break the lock to enter the inspection.
(6) alarm location in the mall independent stores and has been locked, instantly report to the supervisor on duty and the person in charge of the mall on duty, and stay on the scene to observe, wait for the supervisor on duty and the person in charge of the mall on duty to decide whether to break the lock into the inspection.
3. After receiving the report from the security guards of the fire monitoring center, the supervisor on duty will lead the mobile personnel to the alarm location as fast as possible for on-site inspection.
(1) After the alarm location site inspection, confirmed to be false alarms, immediately notify the fire monitoring center security guards on duty to reset, if you enter the office unit, store, parking lot inspection, you need to explain to the user, apologize before leaving.
(2) alarm location in the office building units or shopping malls and independent stores and has been locked, if you observe a fire or smoke, you must break the locks to enter the scene to check, remove the risk of locking, and notify the user.
(3) After the on-site inspection is confirmed as a fire, according to the initial fire handling procedures.
4. The security guard on duty at the fire monitoring center will reset the signal after receiving the instruction from the supervisor on duty and make a record.
6, the initial fire handling procedures
1. found that the initial fire, the presence of personnel should be:
(1) immediately report to the building fire monitoring center, the report includes the specific location of the fire, the nature of the burning material, the direction of the fire spread, etc.
(2) immediately use the nearby fire-fighting equipment to fight and try to control the development of the fire;
(3) If possible, close the doors and windows to slow down the rate of fire spread.
2. Upon receipt of the on-site report, the security guard on duty at the Fire Monitoring Center:
(1) Report to the supervisor on duty immediately;
(2) Contact the head of the Security Department to report the situation;
(3) Closely monitor the situation of the alarm location.
3. Upon receipt of the fire alarm report, the supervisor on duty:
(1) leads the firefighters to arrive at the fire scene with fire extinguishers as fast as possible;
(2) immediately directs the personnel present to extinguish the fire;
(3) directs the evacuation of people at the fire scene and those who may be affected by it by using fire escape ladders.
4. After extinguishing the fire, the supervisor on duty arranges for the personnel to stay at the fire scene and wait for the company to investigate.
5. If the fight is ineffective, the supervisor on duty immediately decides:
(1) to evacuate the fire-fighting personnel to a safe distance;
(2) to report to the supervisor immediately;
(3) to enter the fire emergency treatment program.
Seven, fire emergency treatment program
Initial fire fighting is ineffective, the fire can not be controlled and further spread, the presence of the supervisor should be instantly reported to the highest supervisor on duty in the building.
1. Upon receiving the report, the highest supervisor on duty of the building:
(1) immediately summon the volunteer firemen in the building, and order the leaders of each group of the volunteer firemen to lead the personnel of the group to take their positions;
(2) issue instructions to the fire center, and notify the users to evacuate urgently with the emergency broadcasting system;
(3) arrive at the scene at the first time, and decide whether to call the fire department for help. Fire Department to call the police for help.
2. After receiving the instruction from the highest supervisor on duty of the building, the duty of the fire monitoring center of the building:
(1) activate the fire emergency broadcasting to notify the users of the emergency evacuation;
(2) call the police to the fire department of the city to make it clear the location of the building, the floor where the fire started, the fire, and so on;
(3) set the monitoring camera at the floor where the fire started to monitor closely;
(4) check the elevator for trapped people;
(4) check the elevator to see whether it is trapped or not. (4) check the elevator for trapped people, if the elevator is trapped, immediately report to the supervisor on duty, and use the elevator intercom to stabilize the trapped person's mood.
3. Rapid action group after receiving the command:
(1) to reach the scene as fast as possible, organize the fire extinguishing;
(2) close the fire doors or shutters of the fire zones;
(3) arrange for the personnel to carry fire-fighting tools to check the adjacent rooms and up and down the floor passages to check whether there is a spread of fire;
(4) for the nature of the burning Different take corresponding fire extinguishing methods.
4. medical evacuation group received the command command:
(1) direct the user evacuation, the evacuation order first from the fire above the floor of each start, to appease the users do not need to evacuate the floor;
(2) guide the fire room or floor safety evacuation, followed by checking for leaks;
(3) guide the user from the fire escape ladder evacuation to the first floor, can not be evacuated from the fire escape ladder to the first floor;
(5) the user can not be evacuated from the fire escape ladder to the first floor, but the fire escape ladder to the fire escape ladder to the first floor. Fire escape ladder evacuation to the first floor, guide users to evacuate to the rooftop upwind waiting for rescue, and organize water gun cover;
(4) medical rescue team with first aid medicine and equipment to the evacuation of the centralized point.
5. security guard group received the command work instructions:
(1) clear the barricades, directing unrelated vehicles to leave the scene, and maintain the order of the building to the perimeter;
(2) prohibit unrelated people from entering the building, and direct the evacuees to leave the building;
(3) waiting to guide the firefighters of Fire Services Bureau to the scene of the fire.
VIII. Investigation Procedures of Fire Accidents
1. After the initial fire is dealt with
(1) Take photos of the scene;
(2) Stay at the scene;
(3) Investigate the cause of the accident;
(4) Pursue the person responsible for the fire to make financial compensation;
(5) Apologize to the affected users;
(6) Make a record of the accident.
2. After the fire is extinguished
(1) protect the scene, prohibit unrelated persons from entering the scene;
(2) take photos of the scene;
(3) assist the fire department to investigate the cause of the fire;
(4) explain to the affected users, apologize;
(5) the security department to make a good record of the accident.
3. Common Causes of Fire
(1) Unextinguished smoldering fire;
(2) Improper storage of flammable and explosive substances;
(3) Improper use of electricity, resulting in sparks;
(4) Substandard electrical products;
(5) Spontaneous combustion of goods accumulated for a long time.
4. Accident records are kept in duplicate, one by the Security Department and one by the Administration Office.
5.