How to run Siemens KP1200 touch screen online on Perten, just set up Ethernet communication parameter in the connection of the screen, and click the emulation button to run the screen program.
How to control Siemens operator panel remotely via PC or smart phone.
Taking Siemens delicate panel KP1200 as an example, it introduces how to skillfully realize remote control of operation panel by computer or cell phone.
Pre-requisite preparation.
1. Install the license.
Install the Siemens license WinCC Sm@rtServer for SIMATIC Panel to your PC. The source of the license can be searched online.
?2. Establish the connection.
Use a network cable to establish a connection between the PC and the HMI, set the IP address of the two in the same network segment, and set the communication mode of the HMI to Ethernet, do not use the PN/IE mode (PN/IE can not be connected through the authorization manager). Through the Authorization License Manager Automation License Manager menu bar - Edit - connect to the target system - connect to the HMI device.
Select KP1200Comfort according to the device type of HMI, the connection method is Ethernet, enter the IP address of HMI, and then click Finish button.
3. Transmit Authorization.
After the connection is successful, select the authorization from step 1, right click on Transmit, select KP1200 and click OK.
At this point, the authorization will be transferred to the KP1200, and the authorization on the computer side will disappear.
Also check on the HMI to see if the authorization has been successfully transferred.
Program Configuration.
Open the KP1200 project program, activate "Start Sm@rtServer" in the program by running System Settings-Services, save it and download it to the KP1200.
HMI's control panel.
After the program is downloaded, open the settings screen in the control panel of KP1200 via "Settings->WinCC Internet Settings".
Operation panel settings.
Set the remote password.
Select the Remote tab and click on the Change settings button i. Set the password for accessing the Server in this tab, select the Administration tab, in this tab you can set the mandatory password Select the "Administration" tab, and in this tab you can set a mandatory password "Password needed".
This setting is used to control forced access in case of emergency. You can also set an "Active user timeout".
Password suggestion: Password1: 123 Password2: 456.
Computer control.
Get the SmartClient.exe application from the SIMATIC WinCC flexible 2008 or TIA WinCC software CD. The application is installation free and is opened by double clicking on it.
Enter the IP address of the HMI and the password set in section 1.3.2 and click Connect.
The application can be used to synchronize the display of the HMI screen, switch the screen, exit the screen, and operate the internal interface of the HMI.
Smartphone control.
Take Android phone as an example to introduce. Search SIMATIC WinCC Sm@rtClient through 360 and other cell phone application markets.
Introduction of APP software.
Click the plus sign in the upper right corner to add services. Note: The default port number is: 5900, don't change it.
Set your phone to auto-rotate to enable landscape view operation.