1 medical building lighting design to implement the relevant national norms, to meet the green lighting requirements.
2 Recommended values of illumination are shown in Table 2 Figures for the recommended illumination (lx)
Night guardian lighting 5
Ward 50
Hou consulting room, patient activity room, radiology diagnostic room, nuclear medicine, physical therapy room, guardianship wards 150
Consultation room, examination room, laboratory, pathology, formula room, doctor's office, nurses' room, duty room, CT diagnostic room, radiology treatment room 200
Operating room 500
3 medical building medical rooms should be used for high color rendering lighting fixtures, color rendering index ≥ 80. preferably with electronic ballasts T8, T5 tri-color fluorescent lamps.
4 color temperature of the light source number for the color temperature (K)
Wards, patient activity rooms, physical therapy rooms, custody wards, dining room ≤ 3300
Consultation room, waiting room, laboratory, pathology, formula room, doctor's office, nurse's office, duty room, radiology diagnostic room, nuclear medicine, CT diagnostic room, radiology treatment rooms, operating rooms, equipment rooms 3300 -5300
5 Medical building lighting system using fluorescent lamps should be the harmonics of the system should be calibrated to meet the relevant national standards.
6 Ward lighting should be used indirect lamps or reflective lighting. Bed should be set up for local lighting, a bed, a lamp, bedside control.
7 nursing unit aisles, consultation rooms, treatment, observation, ward and other places lamps, should avoid glare on bedridden patients, it is appropriate to use diffuse reflective lamps.
8 nursing unit aisles and wards should be equipped with "night lighting", the bedside part of the illumination should not be greater than 0.1lx, pediatric wards should not be greater than 1lx.
9 need to observe the patient x-ray diagnostic room, gas pedal treatment room, nuclear medicine scanning room and γ camera room, operating rooms and other rooms, should be equipped to prevent misdirection. Red signal light to prevent accidental entry, and its power supply should be connected to the unit.