ABB frequency converter how to set for the parameters?

ABB inverter parameter settings are as follows:

A, inverter simple and simple local start

1. First make sure that the air switch is closed, the contactor is energized;

2. Press LOC/REM to make the inverter for the local control mode

3. Press PAR to enter the parameter setting mode of the control panel

Use the double arrow keys to choose to the 99 parameter group, then use the single arrow key to select 04, ENTER to enter

99.04 Motor Drive Mode (DTC)

The DTC inverter is set to rotational speed (in most cases this mode is used)

The SCALA inverter is set to frequency

Press ENTER to confirm the selection of the mode (to cancel press ACT to return)

Press PAR to enter the control panel's parameter setting mode

3. Return)

4. Press ACT to return to the current state

5. Press REF, select the up and down adjustment keys, enter the specified parameters and then press ENTER to confirm?

6. Press the start button, the inverter starts

So far, it completes a simple local running process of an inverter

If you need to replace the displayed actual signal with other actual signals, you can operate according to the following steps:

1. Press ACT to enter into the display mode of the actual signal;

2. Select the parameter line to change, press ENTER to change the parameter line, and press ENTER to confirm. Press ACT to enter the actual signal display mode;

2. Select the parameter line that needs to be changed and press ENTER to enter;

3. Press the single and double arrow keys to select the parameter to be displayed or to change the parameter group;

Several commonly used display signals:

01.02 Actual speed of the motor SPEED

01.03 Actual value of the input frequency of the transmission FREQ

03.20 Code for the last fault of the frequency converter LAST FLT (The code of the last fault LAST FLT)

4. Press ENTER to confirm and return to the actual signal display mode; (Cancel and press ACT directly)

II. Uploading and Downloading

How can you set up the motor to be uploaded to the CDP-312 operation panel:?

1. Activate the communication of optional devices

Confirm that 98.02 COMM.MODULE LINK is set to FIELDBUS

98.07 COMM PROFILE is set to ABB DRIVES

2. Press LOC/REM to switch to L local control state;

3. Press FUNC to enter function mode;

4. Press the single and double arrow keys to enter the UPLOAD function press ENTER to perform the upload, and automatically switch to the current signal display mode when finished;

5. Make sure that the control panel is in the Remote Control Mode state (which can be changed by pressing LOC/REM) if you want to move the control panel away from a drive unit before doing so

How to download data from the control panel to the transmission unit:

1. Connect the control panel with data to be uploaded to the transmission unit;

2. Confirm that it is in the local control mode (can be changed by pressing LOC/REM);

3. Press FUNC to enter into the function mode;

4. Enter into the DOWNLOAD download function and press ENTER to execute the download. to execute the download.

Three, PLC and inverter PROFIBUS-DP communication

In order to realize the communication between inverter and PLC, first make sure that the communication template has been installed, and then install the DP network cable.

At this time, you need to set and confirm the following parameters in the local mode (press LOC/REM to select): (press FAR to enter the parameter selection

mode, use single and double arrows to select, ENTER key to enter the parameter or parameter group setting)

1. 98.02 COMM.MODULE LINK Select FIELDBUS this one value. Indicates that the RPBA-01 communication touch panel is activated; 98.07 COMM PROFILE selects the value of ABB DRIVES, which serves to select the communication protocol of the drive unit;

2. 10.01 EXT1 STRT/STP/DIR selects the value of COMM.CW Defines the external control ground for the connection of commands for starting, stopping and steering and the signal source;

3, 10.02 Same as 10.01;

4, 10.03 REF DIRECTION Define the steering of the motor

FORWARD Forward?

REVERSE Reverse

REQUEST promises user-defined steering (selected);

5. 16.01 Run Enable is set to YES;

6. 16.04 FAULT RESET SEL selects the source of the signal for the fault reset to be COMM. CW (fieldbus control). This parameter is active if 10.01 and 10.01 have been set to COMM.CW;

7, 11.02 EXT1/EXT2/ SELECT selects the control source value for the control word as COMM.

11.04 EXT REF1 MINIMUM sets the minimum speed value of the motor to 0rpm;

11.05 EXT REF1 MAXIMUM sets the maximum speed value of the motor to 1400rpm;

9, 22.01 ACC/DEC SELEChooses the current acceleration/deceleration time value as ACC/DEC 1;

10, 22.02 ACCEL TIME1 defines the value of the acceleration time as 1.50s;

11, 22.03 STOP FUCTION defines the value of the deceleration time as 0.50s;

12, 51This set of parameters is only visible if a fieldbus adapter module has been installed and the module has been activated by parameter 98.02.

51.01 Communication protocol value is PROFIBUS-DP;

15, 51.02 Value is the address of the frequency converter;

16, 51.03 Communication rate value is 1500 (1.5 mbpa);

17, 51.04 DP communication protocol value is PPO4;

National free service hotline inquiry. 4008818160?

18, 51.05 (PZD3 OUT) to 3;

19, 51.06 (PZD3 IN) to 6;

20, 51.07 (PZD4 OUT) to 7;

21, 51.08 (PZD4 IN) to 10;

22, 51.09 (PZD4 IN) to 10;

22、51.09 (PZD5 OUT) change to 8 ;

23、51.10 (PZD5 IN) change to 11 ;

24、51.11 (PZD6 OUT) change to 9 ;

25、51.12 (PZD6 IN) change to 12;

26、92.01 302(fixed);

27, 92.02 102 The actual speed value of the frequency converter is sent as the second word (ACT1) of the main actual signal

28, 92.03 104 The actual current value of the frequency converter is sent as the third word (ACT2) of the main actual signal

29, 92.04 110 The temperature value of the IGBT is sent as the first word (ACT3) of the auxiliary actual signal ( ACT3) is sent?

30, 92.05 320 to the last fault code as the second word of the auxiliary actual signal (ACT4) sent after the setup to observe the communication template status lamp status, at this time, if the two light two green lamps, indicating that the communication is successful; there are red lamps, indicating that the communication fails.

Four, some of the parameters of the inverter settings

1, speed limit value and acceleration, deceleration work

20.01 minimum speed

20.02 maximum speed

22.02 acceleration time

22.03 deceleration time

22.04 acceleration time

22.05 Deceleration time

2. Blocking protection

30.10

30.11

30.12

3. Underload protection

30.13

30.15

4. Motor missing items

30.16

5, Communication failure

30.18

30.19

30.20

30.21

6. Parameter lock

User-enabled parameter locking function prevents mis-adjustment of the parameters

16.02

16.03

For detailed information, please refer to ACS800 Standard Application 7.0X

V. PROFIBUS-DP Field Controller (PLC) Settings

1. Install the ABB inverter GSD file ABB_0812.GSD;

2. Add the slave station ABB Drives in the system PROFIBUS-DP hardware configuration. RPBA-01, station number 2 (or other station number) insert PPO Type Module 4;

3. In the parameter setting of slave station 2 (or other), change Operation Mode to Vendor Specific (i.e., ABB Drives protocol);

4. Other than the default configuration;

5. Download the configuration to the master station.

6. The data in the input area (OUTPUT) from the master to slave 2 is thus constructed as follows:

Output:

Meaning:

The first word

Control word CW for the ABB drive communication protocol

The second word

The given value of the frequency converter REF1

Third word

Feed value of the frequency converter REF2

Fourth word

Feed value of the frequency converter REF3 (determined by the ACS800 frequency converter parameter 90.01)

Fifth word ?

The given value of the frequency converter REF4 (determined by ACS800 frequency converter parameter 90.02)

Sixth word

The given value of the frequency converter REF5 (determined by ACS800 frequency converter parameter 90.03)

7. The data in the input area (INPUT) of the master to the slave 2 is constructed as follows:

Input:

Meaning:

First word

Status word SW used for the ABB drive communication protocol

Second word

Actual value of the frequency converter ACT1 (determined by ACS800 frequency converter parameter 92.02)

Third word

Actual value of the frequency converter ACT2 (determined by ACS800 inverter parameter 92.03)

Fourth word

Actual value of the inverter ACT3 (determined by ACS800 inverter parameter 92.04)

Fifth word

Actual value of the inverter ACT4 (determined by ACS800 inverter parameter 92.05)

Sixth word

Actual value of the frequency converter ACT5 (determined by ACS800 frequency converter parameter 92.06)

PLC and frequency converter communication - PLC side application

PPO4

ACS800-ABB Drives RPBA-01

Control word 1 unused bit according to description section: constant 0 or constant 1 is already written in the db and does not need to be changed

Control word w#16#476 when ready to close

Control word w#16#477 when closed but not in operation

Control word w#16#47F when in operation