Elevator emergency plan template (general 5)
In the weekday study, work and life, there will inevitably be accidents, in order to reduce the consequences of accidents, often according to the specific circumstances of the pre-programmed emergency plan. How to write an emergency plan to play its role? The following is my collection of elevator emergency plan template (General 5), for reference only, I hope to be able to help you.
Elevator emergency plan 1
First, the general principles
1.1 Preparation of the purpose
To further strengthen the hospital elevator safety supervision, and effectively do a good job in the hospital's safety management and prevention of emergency elevator accidents and emergency response, to ensure that in the case of an elevator failure occurs, the whole hospital departments, departments and emergency response Disposal work quickly and orderly, minimize casualties and protect the health and safety of employees and patients.
1.2 Preparation of the basis
Elevator is an important means of transport in high-rise buildings, once the failure, the passengers are very likely to cause panic and other dangerous accidents. In order to ensure that the hospital elevator in the event of failure to get correct and effective and rapid organization of emergency rescue work, minimize the hazards of passenger safety accidents, according to the "People's Republic of China *** and the State Safety Production Law", the Ministry of Health "disaster prevention and emergency disposal of medical and health care institutions guidance", with reference to the "National Emergency Healthcare Rescue Emergency Response Plan for Public **** Events", "Jiangsu Province, the emergency public **** events overall emergency response plan". The provisions of the overall emergency response plan for public *** events in Jiangsu Province, etc., the formulation of this plan.
1.3 Scope of application
This plan applies to the hospital's elevator safety management, elevator accident prevention and emergency response work.
1.4 Guiding ideology and working principles
Hospital elevator accident emergency response should adhere to the principle of people-oriented, life first; rapid response, decisive disposal of the principle of scientific response, the principle of reducing losses; division of labor, responsibility, the principle of responsibility. Ensure that the hospital elevator emergencies can be timely, rapid, efficient and orderly treatment.
Second, the emergency organization and command structure
2.1 The hospital set up an elevator failure emergency treatment leading group.
Hospital emergency leadership group
Leader: President
Members: Vice President, functional section chief
2.2. Emergency treatment leading group main responsibilities: check and urge the responsible person of each department to do a good job in emergency precautions and emergency preparedness. According to the actual situation and work to develop emergency treatment work program. Discuss and decide on major issues in the work of emergency response, coordination of human and material resources, organization and implementation of emergency response and rescue, if necessary, to the relevant units to send a request for rescue.
2.3 In order to ensure that the emergency treatment work is carried out in an orderly manner, the hospital set up: the elevator failure emergency office, emergency repair team and emergency supplies to protect, safety and security team, emergency rescue team, the emergency office is located in the General Affairs Section, the specific composition of the personnel are as follows:
2.3.1. Elevator failure Emergency Office Director by the comrade concurrently.
Responsibilities: Responsible for the rapid communication of the hospital leading group instructions, a comprehensive understanding of the actual situation of the accident, timely report to the leading group, coordination and communication of the work of the working group.
2.3.2 Emergency repair group and emergency materials security
Group leader: General Affairs Section
Group member: logistics support team leader
Responsibilities: in the elevator accident, is responsible for quickly contacting the elevator maintenance company to hospital repair and disposal. Before the rescue, the first will be trapped in the elevator rescue in the first place, in the rescue of the elevator to give priority to ensure that the surgical elevator recovery. Emergency elevator accident repair process in the supply of materials needed.
2.3.3 emergency ambulance group
Group leader: medical director
Group members: (omitted)
Responsibilities: Responsible for the elevator rescue process, after the completion of the operation need to transport patients en route to safety, and do a good job of ambulance program.
2.3.4. Safety and security group
Leader: Zhu Bin
Members: Jiang Deqiang Wang Yi Ma Yongzhong Chen Jianqing Wang Zhenlin
Zhang Wei Ding Juming
Responsibilities: responsible for organizing the organization of elevator accidents due to the need to transport surgical patients. The elevator accident repair is responsible for maintaining the site order, to prevent human damage and other emergencies, to ensure the smooth progress of emergency rescue work.
Three, emergency disposal program
Hospital **** with four vertical elevators. In case of elevator in the event of failure, the following emergency measures will be taken according to the cause:
3.1. If the elevator in operation due to power failure caused by the stoppage, the elevator operator should quickly call the emergency phone and explain the failure. At the same time to appease the people in the elevator, do not panic, let them wait patiently for rescue. Receive the alarm call personnel, quickly contact the electrician class personnel troubleshooting, restore power supply.
3.2. If the elevator suddenly stops, closes the person, rushes to the top, squats the bottom and other faults in operation, the elevator operator should quickly call the emergency telephone and explain the fault. At the same time, appease the people in the elevator, do not panic, let them wait patiently for rescue. Receive the alarm call personnel, quickly contact the elevator maintenance company to come to the maintenance.
3.3. When the elevator malfunction or accident car trapped, the elevator operator should quickly call the emergency telephone and explain the fault. In the repair personnel are not in place before the emergency security, coordination team personnel should be through the elevator monitoring camera probe to understand the number of people inside the ladder and the situation, to calm the elevator trapped people emotions, do not panic, let it wait patiently for rescue. At the same time, the emergency rescue team personnel in the conditions permit, directing the trained 'full-time personnel first trapped passengers released, closed the elevator safety switch, in the elevator car door obviously placed fault maintenance warning signs, waiting for maintenance professionals to repair.
Fourth, the elevator failure emergency points
4.1 trapped in the elevator, should remain calm, the operator immediately with the elevator alarm, intercom or telephone to contact with the management personnel, waiting for external rescue. If the alarm is ineffective, you can call loudly or intermittently tap the elevator door.
4.2 When the elevator stops running, do not easily pick the door to climb out in case the elevator suddenly opens.
4.3 When water enters the running elevator, open the elevator to the top floor and notify the maintenance personnel.
4.4 If a fire occurs on the way to the elevator, stop the elevator at the nearest floor and quickly use the stairs to escape.
Fifth, the end of the emergency
5.1 After the elevator resumes operation, the elevator maintenance company should carry out a comprehensive safety inspection of the faulty elevator to ensure that the elevator operates normally.
5.2 After the end of the emergency, the elevator class should be summarized on the elevator accidents and handling and other situations reported, and the investigation and analysis of the accident, to find out the cause of the accident, learn a lesson, find shortcomings, sum up the experience, and constantly improve the accident emergency plan.
5.3 in the process of rescue, rescue and disposal, the performance of brave, resourceful, outstanding achievements should be given praise or reward. For in the process of rescue and relief, no reason not in place or late and escape from the battlefield, will be given to penalize administrative sanctions. For those who do not obey the command, will be punished.
5.4 Elevator failure disposal procedures after the incident
5.4.1 Failure to deal with the completion of the handler should be promptly reported to the duty engineer to deal with the processing and the status of the equipment.
5.4.2 Analyze the cause of the failure. For equipment accidents caused by improper use or inadequate maintenance, the relevant team leader should submit a written report to the Director of Engineering.
5.4.3 Do a good job of registering failures in the equipment file.
Six, the basic requirements of emergency personnel
When the hospital elevator occurs more than one or major accidents, the emergency response to each group of personnel in the group leader received a phone call notification, should be quickly rushed to the hospital to participate in the rescue within thirty minutes.
The elevator emergency plan 2
(a) In case of elevator failure, the caretaker first immediately notify the person in charge of the Ministry of Engineering and maintenance personnel, the Ministry of Engineering and maintenance personnel or rescue personnel can be based on different circumstances, try to first release the trapped passengers.
(B) the elevator trapped rescue procedures
1, rescue personnel can be through the walkie-talkie, or cell phone shouting to get in touch with the trapped passengers, be sure to ask the passengers to remain calm, calmly waiting for rescue, trapped passengers can not be any part of the body out of the car. If the car door is in a half-open and closed state, rescuers should try to close the car door completely to prevent accidents.
2, accurately determine the location of the car, ready to rescue. According to the floor indicator, PC display, selector bar or open the door to determine the location of the car, and then try to rescue passengers.
(C) rescue steps
1, the car stops close to the elevator mouth of the position of the rescue steps:
① turn off the power switch in the machine room;
② to open the outer door with a special lock key;
③ in the car on top of the car with manpower to open the door slowly;
④ to help the passengers out of the car;
⑤ to re-close the hall door. ⑤ Close the door again.
2, the car away from the elevator mouth rescue steps:
① into the machine room, turn off the fault potential power switch;
② remove the motor tail shaft end cover, press the handle seat and handle;
③ rescue personnel force to hold the handle, the other rescuer holding a brake release lever, gently pry open the brake, pay attention to the plane mark, so that the car gradually move closest to the hall door (0.5 km). Move closest to the hall door (0.5M) until;
(D) the emergency treatment of abnormal conditions
In the elevator in the event of abnormalities, the passengers must be calm, keep a clear head in order to seek a safer solution.
(V) Disposal in case of fire
①When a fire occurs on the floor, the person on duty in the elevator machine room should immediately try to press the "fire switch", so that the elevator enters into the state of anti-operation; after the elevator operates to the base station, the passengers will be guided to leave the car quickly and notify the engineering department by telephone, and at the same time, call 119.
② shaft or car off the fire, should immediately stop the elevator and guide the passengers to leave, cut off the power supply with a dry powder fire extinguisher or 1211 fire extinguisher; and notify the Ministry of Engineering by phone; if the fire is fierce should immediately call the 119 telephone alarm to ensure that the building's personnel and property safety.
(F) the elevator was flooded when the disposal
① pit by flooding, the elevator should be parked above the second floor;
② floor flooding, the elevator should be parked in the flooding of the previous floor, and then disconnect the power switch and immediately organize the blocking of the water source, the source of the water blocking dehumidification process, such as hot air drying.
③ Finally, with a rocking meter to test the insulation resistance, when the standard, you can try the ladder. After the test ladder is normal, it can be put into normal use.
Elevator Emergency Plan 3
Elevator blackout emergency plan to ensure the safety of doctors and patients to take the elevator, to provide quality service and respond to emergencies and accidents in an orderly manner, the development of the following arrangements:
1, familiar with the elevator maintenance phone;
2, in the event of an accident should first be reported to the elevator maintenance workers and the Ministry of Engineering;
3, the guide staff In the event of an accident should be timely investigation of the operation of the elevator and elevator operation without people inside the situation;
4, and the Department of the guards to get in touch with the use of their personnel and the convenience of communication, to determine the floor and the internal situation of the trapped people, and timely ideological comfort work;
5, the Ministry of Engineering with the elevator maintenance personnel in a timely manner to free the trapped people and repair the elevator;
6, the guide staff in addition to part of the maintenance, others immediately guide passengers to avoid a large number of people crowded in the elevator hall;
7, such as the elevator operation, make every effort to give the maintenance staff, try not to let passengers ride;
8, the Department of the guard at this time should be ready to have the keys to the floor of the elevator room in order to prepare for the use of any time, if possible, it is best to open the door to these floors in advance, so that the maintenance staff can enter at any time. If possible, it is best to open these floor doors in advance, so that the maintenance personnel can enter at any time, and then lock the door after the completion of maintenance;
9, the guide group in the elevator power outage, failure to repair, can not be sure of the recurrence of the failure of the case, you can open the two to four elevators (the elevator must be operated by the guide personnel), and monitor the elevator operation, such as trapped again directly to the floor to the people will be rescued.
Elevator emergency plan 4
In order to enhance the community to deal with the use of elevator operation of all kinds of accidental injuries and trapped people's ability to standardize the specific implementation of the community's emergency rescue plan, the establishment of a sound emergency response system for passenger accidents, standardize the community on the injuries and the trapped accident emergency response work, effective prevention, timely control and elimination of elevator injuries and the hazards of trapped accidents, especially the development of this plan.
1, any employee received the owner alarm or found a passenger trapped in the elevator, should immediately notify the security and fire monitoring room, while recording the time of the report and discovery.
2, security and fire monitoring room after receiving the report should be on the one hand through the monitoring system or intercom to understand the elevator trapped in the location, the number of people trapped, the situation of the people, as well as the elevator floor, on the other hand, through the intercom to the order to maintain the manager of the Department of the or the foreman on duty to report to the Department of the request to send or contact the Ministry of Engineering to rescue.
3, order maintenance department or the foreman on duty after receiving the report, immediately in person or sent to the scene and the trapped passengers to get in touch with the comfort of the passengers, asking passengers to remain calm, patiently waiting for rescue. Especially when the trapped passengers panic or very anxious, trying to pry the door and other extraordinary measures to escape, to patiently caution passengers not to panic and impatient, do not blindly take unnecessary action, so as not to make the failure to expand, dangerous. Note that in this process, the scene can never leave the person, to constantly talk to the trapped person, timely understanding of the trapped person's mood and health status, while promptly reporting the situation to the general manager of the company or the duty leader.
4, the engineering department or the duty officer after receiving the report, should immediately send people to the scene to rescue, if necessary, call the elevator maintenance company to come to repair. If you can not rescue, you should try to take measures to ensure the safety of trapped passengers, waiting for the elevator maintenance company mechanics to rescue.
5, if the engineering department and elevator maintenance company are incapable of rescue or short-term time can not be rescued, depending on the circumstances of the public security department or the fire department for help (should explain the reasons for help and the situation). To the public security, fire department for help before the general manager of the company should be consulted or the consent of the leader on duty.
6, in the rescue process, if you find trapped passengers in someone fainted, unconscious (especially the elderly or children), should immediately notify the medical staff to the scene, so that the trapped people can be rescued after the rescue.
7, after the trapped person rescued, order maintenance minister or shift leader should immediately express their condolences, and understand their physical condition and needs, and at the same time, please provide their name, address, contact phone number and to the cause of the district. If the trapped person does not cooperate to leave on their own, should be recorded for the record.
8, after the trapped person rescued, the Ministry of Engineering should immediately ask the elevator maintenance company to identify the cause of the failure, repair before resuming normal operation.
9, the order maintenance department or the foreman on duty should be recorded in detail after the incident, including the time of receiving the report, the time of the arrival of the order maintainer and maintenance personnel at the scene, the elevator maintenance company notification and arrival time, the time of the rescue of the trapped person, the basic conditions of the trapped person, the elevator resumed normal operation time. If there are public security, fire, medical personnel to the scene, should also be recorded separately to the scene and leave the time, the vehicle number; trapped persons with injuries, should record the injured and was sent to the ` hospital.
10, the engineering department or the duty officer should record in detail the time of the failure, the reason, the solution and repair time.
Elevator Emergency Plan 5Elevator as now people up and down the floor of a means of transport, the safety issue is that we have to pay more attention to, in order to ensure that the elevator equipment is safe, effective and reliable operation, reduce the impact caused by accidents and to avoid the occurrence of accidents with personal injury, Xingtai Elevator has developed this plan. This plan *** is divided into three stages.
First, the accident receiving and disposal procedures
1, the Ministry of Engineering on duty when receiving the accident report should be reported to the reporter to understand the following information: the location of the faulty elevator, whether trapped, trapped in which floor, as well as other important information, and make a good record.
2. The duty officer of the Engineering Department verifies whether the report is correct by telephone to the monitoring room.
3, after confirming that the situation is correct, the duty officer of the engineering department immediately rushed to the scene, and notify the maintenance unit immediately to the scene.
4, with elevator operation qualifications of the personnel with elevator machine room keys, elevator floor keys, communication tools and maintenance tools to the scene to deal with. If necessary, additional personnel on duty to assist.
Second, the elevator fault disposal procedures
1, a, b two fault handling personnel arrived at the elevator machine room and elevator car floor.
2, A: first cut off the main power of the elevator, but must retain the car lighting. Through the elevator machine room of the direct line telephone and the trapped person to get in touch with, tell the trapped person to wait for rescue, do not try to try to leave on their own.
3, B: use the elevator floor door key to open the elevator floor door about 30-40CM, observe the elevator car location.
4. If the elevator car is located within 600cm above and below the level, the trapped person can leave smoothly, and you can directly open the door to help passengers leave.
5, if the car is located in a position other than the above, the trapped person can not leave smoothly, then you need to manually pan the car leveling according to the following steps and then release the passengers.
(1) first calm the passengers, inform the rescue operation is underway, let them wait patiently for rescue.
(2) Remove the protective cover at the end of the elevator traction motor, the special disk car hand wheel set on the motor shaft.
(3) Remove the cover of the brake solenoid, and fasten the release handle to the braking mechanism.
(4) One person grasps the disk handwheel, and one person slowly depresses the release handle to release the brake mechanism. At the same time as the brake mechanism is released slowly turn the disk car handwheel to use the car upward or downward (clockwise disk car, the car upward. Counterclockwise disk car car downward). The brake should be reset when you stop turning the handwheel. It must be noted that: due to the weight imbalance of the car, pan car manually release the brake device to be very careful and slow, to prevent excessive acceleration caused by the loss of control.
(5) turn the lifting mechanism, when the cable on the level marking line and the elevator leveling mark alignment that the elevator car has leveled. At this time, the braking mechanism should be restored.
(6) use the elevator floor door key to open the elevator floor door, release the passengers and then the floor door back to close.
6, by the maintenance unit of the elevator to carry out a comprehensive inspection, to eliminate potential problems before restoring the power into operation
Elevator fault disposal procedures:
1, after the completion of the fault processing, the processor should be timely to the manager of the Ministry of Engineering to report on the processing and the status of the equipment.
2, analyze the cause of the failure. For improper use or maintenance is not in place caused by equipment accidents, the manager of the engineering department to submit a written report.
3, do a good job of fault registration of equipment files.
;