I. Simple and simple local startup of inverter
1. First make sure that the air switch is closed and the contactor is energized;
2. Press LOC/REM to make the inverter local control mode
3. Press PAR to enter the parameter setting mode of the control panel
Select the 99 parameter group with the double arrow keys and then use the single arrow key to select 04. ENTER
99.04 Motor Drive Mode (DTC)
The DTC inverter is set to RPM (in most cases this mode is used)
The SCALA inverter is set to FREQUENCY
Press ENTER to confirm the mode selection (cancel and return to ACT)
4. Press ACT to return to the current status
5. Press ACT to return to the current state
5. Press REF, select the up and down adjustment keys, enter the specified parameters, and then press ENTER to confirm
6. Press the start button, and the frequency converter will start
So far, it has completed the process of a simple local operation of a frequency converter
If it is necessary to replace the actual signals that have already been displayed by other actual signals, you can do it according to the following steps. Operation:
1. Press ACT to enter the actual signal display mode;
2. Select the parameter line that needs to be changed, and press ENTER to enter;
3. Press the single and double arrow keys to select the parameter to be displayed or change the parameter group;
(Commonly used signals are:
01.02 Actual speed of the motor) SPEED
01.03 The actual value of the transmission input frequency FREQ
03.20 The code of the last fault of the frequency converter LAST FLT)
4. Press ENTER to confirm and return to the actual signal display mode; (Cancel by pressing ACT directly)
II. Upload and Download
How to upload a motor that has been set up to CDP? Good motor needs to be uploaded to CDP-312 operation panel:
1. Activate communication of optional devices
Confirm that 98.02 COMM.MODULE LINK is set to FIELDBUS
98.07 COMM PROFILE is set to ABB DRIVES
2. Press LOC/REM to switch to L local control state. REM to switch to L local control state;
3. Press FUNC to enter function mode;
4. Press the single and double arrow keys to enter UPLOAD function Press ENTER to execute upload, and automatically switch to the current signal display mode when finished;
,
5. If you want to remove the control panel from a drive unit, make sure that the control panel is in the Remote control mode (can be changed by pressing LOC/REM)
How to download data from the control panel to the transmission unit:
1. Connect the control panel with data to be uploaded to the transmission unit;
2. Confirm that the control panel is in the local control mode (can be changed by pressing LOC/REM);
3. Press FUNC to enter the function mode;
4. Press FUNC to enter the function mode;
5. FUNC to enter function mode;
4. Enter DOWNLOAD download function and press ENTER to execute download.
Three, PLC and inverter PROFIBUS-DP communication
In order to realize the communication between inverter and PLC, first make sure that the communication template has been installed, and then install the DP network cable.
At this time, you need to set and confirm the following parameters in the local mode (press LOC/REM to select): (press FAR to enter the parameter selection
mode, use single and double arrows to select, ENTER key to enter the parameter or parameter group setting)
1. 98.02 COMM.MODULE LINK Select the value of FIELDBUS. Indicates that the RPBA-01 communication touch panel is activated;
98.07 COMM PROFILE selects the value of ABB DRIVES, which serves to select the communication protocol of the transmission unit;
2. 10.01 EXT1 STRT/STP/DIR selects the value of COMM. CW Defines the connection and signal source for external control ground for start, stop,
steering commands;
3, 10.02 Same as 10.01;
4, 10.03 REF DIRECTION Defines the motor's steering
FORWARD Forward
REVERSE Reverse
REQUEST Promises user-defined steering (this item is selected).
5, 16.01 Run Enable Run Enable
Set to YES;
6, 16.04 FAULT RESET SEL Selects the source of the signal for fault reset
Selected value is COMM. This parameter is automatically
activated if 10.01 and 10.01 have been set to COMM.CW;
7, 11.02 EXT1/EXT2/ SELECT Selects the source of control for the control word
value COMM.CW;
8, 11.03 EXT REF1 SELECT Selects the source of the given value
value is COMM.REF;
11.04 EXT REF1 MINIMUM Sets the minimum speed of the motor
value is 0rpm;
11.05 EXT REF1 MAXIMUM Sets the maximum speed of the motor
value is 1400rpm;
9, 22.01 ACC/DEC SEL selects the current acceleration/deceleration time
value is ACC/DEC 1;
10. 22.02 ACCEL TIME1 defines the acceleration time
value is 1.50s;
11. 22.03 STOP FUCTION defines the deceleration time
value is 0.50s;
12, 51 This set of parameters is only available if a fieldbus adapter module is installed and the module is activated by parameter 98.02
.
51.01 communication protocol value for PROFIBUS-DP;
15, 51.02 value for the frequency converter address;
16, 51.03 communication rate value of 1500 (1.5 mbpa);
17, 51.04 DP communication protocol value of PPO4;
The national free service hotline consulting. 4008818160
18、51.05 (PZD3 OUT) change to 3;
19、51.06 (PZD3 IN) change to 6;
20、51.07 (PZD4 OUT) change to 7;
21、51.08 (PZD4 IN) change to 10;
22 51.09 (PZD5 OUT) changed to 8;
23, 51.10 (PZD5 IN) changed to 11;
24, 51.11 (PZD6 OUT) changed to 9;
25, 51.12 (PZD6 IN) changed to 12;
26, 92.01 302 (fixed);
27, 92.02 102 The actual speed value of the frequency converter is sent as the second word (ACT1) of the main actual signal
28, 92.03 104 The actual current value of the frequency converter is sent as the third word (ACT2) of the main actual signal
29, 92.04 110 The temperature value of the IGBT is sent as the first word (ACT3) of the auxiliary actual signal. ACT3) sent
30, 92.05 320 to the last fault code as the second word of the auxiliary actual signal (ACT4) sent
Set up after the observation of the communication template status lamp status, at this time if two light two green lights, indicating that the communication is successful; there are red
light, indicating that the communication failed.
Four, some of the parameters of the inverter settings
1, speed limit and acceleration, deceleration work
20.01 Minimum speed
20.02 Maximum speed
22.02 Acceleration time
22.03 Deceleration time
22.04 Acceleration time
22.05 Deceleration time
22.05 Deceleration time
2. Blocking protection
30.10
30.11
30.12
3. Underload protection
30.13
30.15
4. Motor missing items
30.16
5, Communication failure
30.18
30.19
30.20
30.21
6. Parameter lock
User-enabled parameter locking function prevents mis-adjustment of the parameters
16.02
16.03
For detailed information, please refer to ACS800 Standard Application 7.0X
V. PROFIBUS-DP Field Controller (PLC) Settings
1. Install the ABB inverter GSD file ABB_0812.GSD;
2. Add the slave station ABB Drives in the system PROFIBUS-DP hardware configuration. RPBA-01, station number 2 (or other station
number) insert PPO Type Module as 4;
3. In the parameter setting of the slave station No.2 (or other), change the Operation Mode to Vendor Specific (i.e.
ABB Drives protocol);
4. Other for the default configuration;
5. Download the configuration to the master.
6. The data in the input area (OUTPUT) from the master to slave 2 is thus constructed as follows:
Output:
Meaning:
First word
Control word CW for the ABB drive communication protocol
Second word
The given value of the frequency converter REF1
Third word
The given value of the frequency converter REF2
Fourth word
The given value of the frequency converter REF3 (determined by the ACS800 frequency converter parameter 90.01)
Fifth word
The given value of the frequency converter REF4 (determined by the ACS800 frequency converter parameter 90.02)
Sixth word
The given value of the frequency converter REF5 (determined by ACS800 frequency converter parameter 90.03)
7. The data in the input area (INPUT) of the master to the slave 2 is constructed as follows:
Input:
Implication:
The first word
is used for the ABB transmission communication protocol Status word SW
Second word
Actual value of the inverter ACT1 (determined by ACS800 inverter parameter 92.02)
Third word
Actual value of the inverter ACT2 (determined by ACS800 inverter parameter 92.03)
Fourth word
Actual value of the inverter ACT3 (determined by ACS800 inverter parameter 92.04)
Fifth word
Actual value of the frequency converter ACT4 (determined by ACS800 inverter parameter 92.05)
Sixth word
Actual value of the frequency converter ACT5 (determined by ACS800 inverter parameter 92.06)
p>PLC and inverter communication - PLC side application
PPO4
ACS800-ABB Drives RPBA-01
Control word 1 unused bit according to the description section: constant 0 or constant 1 is already written in the db no need to change it
Ready to close the gate when the control word w#16#476
Has been Close not running control word w#16#477
Running control word w#16#47F
Welcome to adopt.