Temperature inspector connected to the RTD display negative how to deal with!

1, fault phenomenon: display meter indicates negative value;

Possible causes: display meter and pt100 RTD wiring is wrong or pt100 RTD has a short circuit phenomenon;

Treatment: correct wiring, or find out where the short-circuit, strengthen the insulation.

2, fault phenomenon: pt100 RTD table indicates infinity;

Possible causes: pt100 RTD or lead wire short circuit or loose terminals, etc.;

Treatment: replacement of the resistor body or welding and tightening of the wiring screws and so on.

3, the failure phenomenon: display pt100 RTD indication value than the actual value of low or unstable value;

Possible causes: the protection of the tube metal chips, dust, dirt between the terminals and RTD short-circuit;

Processing methods: remove the metal chips, dust, water droplets, etc., to find the short-circuit point to strengthen the insulation.

4, failure phenomenon: pt100 thermal resistance value and temperature changes;

Possible causes: pt100 thermal resistance wire material corrosion and deterioration;

Treatment: replacement of the pt100 RTD.