Legal analysis: a total residual chlorine of infectious tuberculosis implementation of 0.5mg / l (direct discharge into the water body requirements).
1, using chlorine-containing disinfectant disinfection process control requirements are:
Disinfection contact pool contact time 1.5h, contact pool exit total residual chlorine 6.5-10mg/l
2, using other disinfectants on the total residual chlorine does not require.
Two, comprehensive medical institutions and other medical institutions total residual chlorine implementation of 0.5mg / l (direct emissions requirements), indirect emissions do not require.
1, the use of chlorine disinfectant disinfection process control requirements are:
Emission standards: disinfection contact pool contact time 1h, contact pool outlet total residual chlorine 3-10mg/l.
Pre-treatment standards: disinfection contact pool contact time 1h, contact pool outlet total residual chlorine 2-8mg/l.
2, the use of other disinfectants do not require the total residual chlorine. Do requirements.
Legal basis: "Chinese People's **** and the State Water Pollution Prevention and Control Law"
Article 10 of the discharge of water pollutants, shall not exceed the national or local water pollutant discharge standards and key water pollutant discharge total control indicators.
Article 11 Any unit or individual has the obligation to protect the water environment, and has the right to report the pollution and damage to the water environment. People's governments at or above the county level and its relevant competent departments in the prevention and control of water pollution to make significant achievements in units and individuals to be recognized and rewarded.