"National construction engineering seismic defense classification standard" this standard by the Ministry of Housing and Urban-Rural Development is responsible for the management of the mandatory provisions of the interpretation of the Chinese Academy of Building Research Institute of Engineering Seismic Research Institute is responsible for the interpretation of the specific technical content. The following is the full text of the "national standard for seismic defense classification of building projects":
The Chinese people*** and the national standard for seismic defense classification of building projects
1 General Provisions
1.0.1 In order to clearly define the seismic design of building projects, the category of defense and the corresponding seismic defense standards, in order to effectively mitigate seismic hazards, the development of this standard.
1.0.2 This standard applies to the classification of seismic defenses for building projects in seismic defense zones.
1.0.3 All construction projects in the seismic defense zone should determine its seismic defense category.
New construction, alteration and expansion of building works, its seismic defense category should not be lower than the provisions of this standard.
1.0.4 The formulation of industry standards for the classification of seismic defenses for construction works shall comply with the division principles of this standard.
Building projects with special requirements not listed in this standard shall be classified according to the special provisions for seismic defenses.
2 Terminology
2.0.1 Seismic fortification classification Seismic fortification category for structures
According to the building suffered an earthquake damage, may cause casualties, direct and indirect economic losses, the degree of social impact and its role in earthquake relief, etc., for the The division of defense categories made by various types of buildings.
2.0.2 Seismic fortification intensity
Approved by the state authority as a basis for seismic fortification of an area of seismic intensity. In general, take 50 years beyond the probability of 10% of the earthquake intensity.
2.0.3 Seismic fortification criteria Seismic fortification criterion
Measurement of seismic fortification requirements of the scale, by the seismic fortification intensity or design of ground shaking parameters and building seismic fortification category to determine.
3 Basic Provisions
3.0.1 The classification of seismic protection category of the building shall be determined according to the comprehensive analysis of the following factors:
1 The magnitude of casualties, direct and indirect economic losses, and social impacts caused by building damage.
2 The size of the town, the characteristics of the industry, the scale of industrial and mining enterprises.
3 The size of the scope of the impact on the overall situation after the failure of the building use function, the impact of earthquake relief and the difficulty of recovery.
4 The importance of the building sections are significantly different, can be divided into seismic defense categories by section. The lower section of the category should not be lower than the upper section.
5 The same building in different industries, when the position and the consequences and impact of earthquake damage are different, its seismic defense category may not be the same.
Note: Sections refer to structural units separated by seismic joints, parts with different functions of use in the plane, or parts with different functions of use above and below.
3.0.2 The building works shall be divided into the following four seismic defense categories:
1 special defense category: refers to the use of special facilities, involving the national public **** security of major construction projects and earthquakes may occur serious secondary disasters and other particularly significant consequences of disasters, the need for special defense of the building. Abbreviated category A.
2 key defense category: refers to the earthquake function can not be interrupted or need to be restored as soon as possible lifeline-related buildings, as well as earthquakes may lead to a large number of casualties and other major disasters, the need to raise the standard of defense buildings. Referred to as Category B.
3 standard defense category: refers to a large number of in addition to 1, 2, 4 paragraphs in accordance with the standard requirements for the defense of the building. Abbreviated category C.
4 moderate defense category: refers to the use of few people and earthquake damage does not cause secondary disasters, allowing a moderate reduction in certain conditions of the requirements of the building. Abbreviated category D.
3.0.3 The seismic defenses of the seismic category of buildings should meet the following requirements:
1 standard defenses, should be determined according to the seismic intensity of the region's seismic measures and seismic effects to achieve the encounter higher than the local seismic intensity of the predicted rare earthquakes do not cause the collapse of the earthquake or the occurrence of life-threatening damage to the seismic defense objectives.
2 key defense category, should be higher than the seismic intensity of the region to strengthen its seismic measures; but the seismic intensity of 9 degrees should be higher than the 9 degree requirements to take seismic measures; foundation seismic measures, should be in line with the relevant provisions. At the same time, it should be determined according to the seismic intensity of the region to determine its seismic role.
3 Special defense category, should be higher than the seismic intensity of the region to increase the requirements of one degree to strengthen its seismic measures; but the seismic intensity of 9 degrees should be higher than the requirements of 9 degrees to take anti-seismic measures. At the same time, according to the approved seismic safety evaluation results and higher than the requirements of the seismic intensity of the region to determine its seismic role.
4 moderate defense category, allowed than the requirements of the seismic intensity of the region to appropriately reduce its seismic measures, but the seismic intensity of 6 degrees should not be reduced. In general, the seismic effect should still be determined according to the seismic intensity of the region.
Note: For the key defense class and the scale of the industrial building is very small, when changed to better seismic performance of the material and meet the seismic design code of the structural system requirements, allowing the standard defense class defense.
3.0.4 This standard only lists the main industry seismic defense category of the building examples; use function, scale and examples of similar or similar buildings, according to the example of its seismic defense category. This standard is not listed in the building should be classified as a standard defense category.
4 disaster prevention and relief buildings
4.0.1 This chapter applies to urban and industrial and mining enterprises and disaster prevention and relief related buildings.
4.0.2 Disaster prevention and relief buildings shall be divided into seismic defense categories according to their social impact and their role in earthquake relief.
4.0.3 The seismic protection category of medical buildings should be consistent with the following provisions:
1 Tertiary hospitals in the outpatient clinic, medical technology, inpatient housing, seismic protection category should be categorized as a special class of protection.
2 two, three hospital outpatient, medical technology, inpatient housing, with surgical operating room or emergency department of the township hospital medical housing, county-level and above the emergency center of the command, communication, transportation system of the important buildings, county-level and above the independent blood collection and supply institutions of the building, seismic defenses should be classified as a key type of defense.
3 Industrial and mining enterprises, medical buildings, can be compared to the city's medical building example to determine its seismic defense category.
4.0.4 Fire fighting garage and its duty room, the seismic defense category should be classified as key defense category.
4.0.5 In towns with a population of more than 200,000 and the main buildings of disaster prevention and emergency command centers in counties and county-level cities, the seismic fortification category shall not be lower than the key fortification category.
Industrial and mining enterprises of the disaster prevention and emergency command system building, can be compared to the city disaster prevention and emergency command system building example to determine its seismic fortification category.
4.0.6 The seismic fortification category of the building of the Center for Disease Prevention and Control shall be in accordance with the following provisions:
1 The building of the Center for Disease Prevention and Control that undertakes the task of researching, pilot testing, and storing the highly toxic and high-risk infectious disease viruses, or its section, shall be classified as a special fortification category.
2 does not belong to paragraph 1 of the county, county-level cities and above, the main building of the Center for Disease Control and Prevention, seismic fortification category should be classified as key fortification category.
4.0.7 The seismic fortification category of a building used as an emergency shelter shall not be lower than the key fortification category.
5 Infrastructure Buildings
5.1 Water Supply and Drainage, Gas and Heat Buildings in Towns and Cities
5.1.1 This section applies to water supply, drainage, gas and heat construction works in towns and cities.
Industrial and mining enterprises of water supply, drainage, gas, heat construction works, respectively, can be compared to the city of water supply, drainage, gas, heat construction works to determine its seismic defense category.
5.1.2 The water supply, drainage, gas and heat buildings of cities, towns and industrial and mining enterprises should be divided into seismic defense categories according to their functions, scale, ease of repair and social impact. Its supporting power supply building, should be the same as the main building seismic defense category.
5.1.3 water supply construction projects, more than 200,000 people in towns, seismic intensity of 7 degrees and above the county and county-level cities of the main water facilities and water pipelines, water purification and treatment plant of the main water treatment buildings (structures), water distribution wells, water supply pumping station, control room, laboratory, etc., seismic defenses should be classified as a key defense category.
5.1.4 Drainage construction projects, more than 200,000 people in towns and cities, seismic intensity of 7 degrees and above the county and county-level cities of the sewage trunk (including merging), the main sewage treatment plant of the main water treatment buildings (structures), water pumping room, central control room, laboratory, and urban drainage pumping station, the town of rainwater pumping stations in the intersection of the main road, the seismic category should be classified as a key type of defense.
5.1.5 gas building, more than 200,000 people in towns, counties and county-level cities of the main gas plant's main plant, storage tanks, pressurized pump room and compression room, scheduling building and the corresponding ultra-high-pressure and high-pressure pressure regulator, high-pressure and high-pressure gas pipelines and other major facilities, seismic defenses should be classified as a key type of defense.
5.1.6 In thermal buildings, the main plant, dispatching building, relay pumping station and the corresponding main facilities of the main thermal plant in towns of more than 500,000 people should be categorized as key seismic defenses.
5.2 Electric Power Buildings
5.2.1 This section applies to electric power production buildings and urban power supply facilities.
5.2.2 Electric power buildings shall be divided into seismic defense categories according to the scope of cities and enterprises directly affected by them and the direct and indirect economic losses caused by earthquake damage.
5.2.3 The seismic protection category of the power dispatch building shall comply with the following provisions:
1 For national and regional power dispatch centers, the seismic protection category shall be classified as special protection category.
2 Provinces, autonomous regions and municipalities directly under the Central Power Dispatch Center, seismic protection category should be classified as a key defense category.
5.2.4 Thermal power plants (including nuclear power plants, conventional island), substation production buildings, the following buildings should be classified as key seismic defense category:
1 stand-alone capacity of 300MW and above, or the planning capacity of 800MW and above, thermal power plant and earthquake must maintain normal power supply to the important power facilities of the main plant, the electrical complex, Network control building, scheduling and communication building, distribution equipment building, chimneys, flue gas, coal crusher room, coal transfer station and coal transfer trestle, fuel oil and gas unit power plant fuel supply facilities.
2 Main control communication building, distribution plant building and in-situ relay rooms in substations of 330kV and above and hub substations of 220kV and below; main control communication building, valve halls and in-situ relay rooms in converter station projects of 330kV and above.
3 The main power generation and distribution control room and its power supply and heat supply facilities of the thermal power station supplying centralized heat supply for towns with a population of more than 200,000 people.
4 Communication dispatch buildings that should not interrupt communication facilities.
5.3 Transportation Buildings
5.3.1 This section applies to railroads, highways, water transport and air transport system buildings and urban transportation facilities.
5.3.2 Transportation system production buildings should be based on its position in the transportation line, the degree of difficulty in repair and the role of rescue and disaster relief, restoration of production played a role in the division of seismic defenses category.
5.3.3 Railway buildings, high-speed railroads, passenger lines (including intercity railroads), passenger and freight **** line Ⅰ, Ⅱ main line and freight line of the railroad hub of the train scheduling, operation, communications, signaling, power supply, water supply buildings, as well as mega-stations and the highest number of people gathered in a large number of large stations of passenger terminal, seismic defenses shall be classified as a key defense category.
5.3.4 Highway buildings, highways, first-class highways, first-class bus terminals and highway monitoring rooms located in areas where the seismic intensity is 7 degrees and above, and first-class long-distance bus station passenger terminal buildings, seismic defenses should be classified as key defenses.
5.3.5 water transport buildings, more than 500,000 people in the city, is located in the seismic intensity of 7 degrees and above, such as water transport communication and navigation and other important facilities of the building, the national important passenger terminals, sea rescue and salvage departments such as important buildings, seismic defenses should be classified as key categories of defense.
5.3.6 Air transportation buildings, international or domestic major trunk airports in the air terminal building, large hangars, as well as communications, power supply, heating, water supply, gas supply, oil supply of the building, seismic defense category should be classified as key defense category.
The air traffic control building defense standards should be higher than the key defense category.
5.3.7 The seismic defenses of urban transportation facilities should be consistent with the following provisions:
1 The large-span bridges that occupy a key position in the transportation network and bear a large amount of traffic should be classified as special defenses; the rest of the bridges in the transportation hubs should be classified as key defenses.
2 urban rail transit underground tunnels, hub buildings and their power supply, ventilation facilities, seismic defenses should be classified as key defensive category.
5.4 Post and telecommunications, radio and television buildings
5.4.1 This section applies to post and telecommunications, radio and television buildings.
5.4.2 Post and telecommunications, radio and television buildings, should be based on its position in the entire information network and the role of ensuring the smooth flow of information network seismic defense category. Its supporting power supply, water supply building, and the main building should be the same seismic defense category; when the special defense category of power supply, water supply building for a separate building, can be divided into key defense category.
5.4.3 The seismic protection category of the post and telecommunications communication building shall comply with the following provisions:
1 International Exit and Entry Bureau, international radio station, national satellite communications earth station, international landing station of the sea cable, the seismic protection category shall be categorized as a special protection category.
2 Provincial centers and provincial centers above the communication hub building, long-distance transmission of the first trunk line hub station, the domestic satellite communications earth station, the local network communication hub building and communications production building, emergency communications building, seismic fortification category should be classified as key fortification category.
3 regional centers and provincial centers of postal hubs, seismic fortification category should be classified as key fortification category.
5.4.4 Broadcasting and television building seismic defense category, shall comply with the following provisions:
1 national and provincial television FM broadcasting tower building, when the height of the concrete tower is greater than 250m or steel tower height is greater than 300m, the seismic defense category shall be categorized as a special defense category; national and provincial level, the rest of the transmitter tower building, seismic defense category should be categorized as a key defense category. The seismic fortification category of the remaining launch tower buildings at national and provincial levels should be categorized as key fortification category. National satellite earth station uplink station, seismic defense category should be categorized as special defense category.
2 national and provincial broadcasting centers, television centers and TV FM radio transmitters of the main building, the total transmission power of not less than 200kW of medium-wave and short-wave radio transmitters, radio and television satellite earth station, national and provincial radio and television monitoring stations and program transmission station of the machine room building and antenna support, seismic defenses should be classified as a key type of defense.
6 Public **** buildings and residential buildings
6.0.1 This chapter applies to sports buildings, theaters, museums, archives, shopping malls, exhibition halls, convention and exhibition centers, educational buildings, hotels, office buildings, scientific experiments, and other public **** buildings, and residential buildings such as houses, dormitories, apartments.
6.0.2 Public **** building, should be based on its degree of concentration of people, the use of function, scale, the size of the social impact and direct economic losses caused by earthquake damage to the division of seismic defense category.
6.0.3 In sports buildings, the stadium with scale classification of extra-large, large, medium-sized stadiums and gymnasiums with a lot of spectator capacity (including swimming pools), the seismic fortification category should be classified as a key fortification class
6.0.4 In cultural and recreational buildings, the large-scale movie theaters, theaters, auditoriums, audio-visual rooms and lecture halls in libraries, and auditoriums and exhibition halls in cultural centers, Entertainment center buildings, seismic protection category should be classified as a key defensive category.
6.0.5 In commercial buildings, large multi-story shopping malls with dense pedestrian flow should be classified as key seismic defenses. When the commercial building and other buildings should be judged separately, and according to the section to determine its seismic defense category.
6.0.6 Museums and archives, large museums, museums storing national cultural relics, special, Class A archives, seismic defense category should be classified as key defense category.
6.0.7 Convention and exhibition buildings, large exhibition halls, convention and exhibition centers, seismic defenses should be classified as key categories.
6.0.8 Education buildings, kindergartens, elementary school, secondary schools, teaching rooms and student dormitories and canteens, seismic defense category should not be less than the key defense class.
6.0.9 scientific experimental buildings, research, pilot production and storage of highly radioactive substances and highly toxic biological products, chemicals, natural and artificial bacteria, viruses (such as plague, cholera, typhoid fever and new high-risk infectious diseases, etc.) of the building, the seismic category should be categorized as a special class of defense.
6.0.10 electronic information center building, provincial and ministerial level preparation and storage of important information building, seismic protection category should be classified as a key defensive class.
The seismic fortification standard of the national information center building shall be higher than the key fortification category.
6.0.11 In high-rise buildings, when the number of regular users in the structural unit exceeds 8000 people, the seismic defense category should be classified as key defense category.
6.0.12 The seismic defense category of residential buildings should not be lower than the standard defense category.
7 Industrial Buildings
7.1 Production Buildings for Coal Mining, Oil Mining and Mining
7.1.1 This section applies to production buildings for coal, oil and gas mining and mining.
7.1.2 Production buildings for coal, oil and gas extraction, and mining shall be divided into seismic defense categories based on the extent of the cities and enterprises they directly affect and the direct and indirect economic losses caused by earthquake damage.
7.1.3 In coal mining production buildings, the lifting, ventilation, power supply, water supply, communication and gas discharge systems of mines shall be classified as key seismic defense categories.
7.1.4 In the oil and natural gas production buildings, the seismic defenses of the following buildings shall be classified as key defenses:
1 Large oil and gas fields, joint stations, compressor rooms, pressurized gas station pumping stations, valves, heating furnace buildings.
2 large computer room and information storage.
3 Oil storage and transportation system liquefied gas station, light oil pump house and nitrogen station, long-distance pipeline first and last station, intermediate pressurized pumping station.
4 Oil and gas fields main power supply and water supply buildings.
7.1.5 Mining production buildings, the following buildings should be categorized as key seismic defense category:
1 large metallurgical mines, fan room, drainage pump room, power substation, power distribution room.
2 Large non-metallic mines, lifting, water supply, drainage, power supply, ventilation and other systems of the building.
7.2 Raw Material Production Buildings
7.2.1 This section applies to industrial raw material production buildings for metallurgy, chemical industry, petrochemical industry, building materials and light industry raw materials.
7.2.2 Metallurgy, chemical industry, petrochemical industry, building materials and light industry raw material production buildings, mainly based on its scale, the ease of repair and the direct and indirect economic losses of the relevant enterprises after the shutdown of the division of seismic defense category.
7.2.3 In the production buildings of metallurgical industry and building materials industry enterprises, the seismic protection categories of the following buildings shall be classified as key protection categories:
1 The power system buildings of large and medium-sized metallurgical enterprises, oil depots and oil pump houses, and the main buildings of plant-wide production control centers and communication centers.
2 Power system buildings of large and medium-sized building materials industry enterprises that do not allow interruption of production.
7.2.4 Chemical and petrochemical production buildings, the following buildings should be classified as key seismic defense category:
1 mega, large and medium-sized enterprises of the main production building and the normal operation of the building plays a key role.
2 Heat, power, gas and water supply buildings of mega, large and medium-sized enterprises.
3 Communication, production command center buildings of mega, large and medium-sized enterprises.
7.2.5 Light industrial raw material production buildings, large pulpboard factory and detergent raw materials factory and other large-scale raw material production enterprises in the main device and its control system and power system building, seismic defense category should be classified as a key defense category.
7.2.6 Metallurgy, chemical, petrochemical, building materials, light industrial raw materials production buildings, the use or production process with highly toxic, flammable, explosive substances in the plant, when there is a leakage of toxicity, explosion or fire hazards, its seismic defenses should be classified as key defense category.
7.3 Processing Manufacturing Production Buildings
7.3.1 This section applies to machinery, ships, aviation, aerospace, electronics (information), textiles, light industry, medicine and other industrial production buildings.
7.3.2 Processing and manufacturing industrial production buildings shall be divided into seismic defense categories according to the size of the building and the magnitude of direct and indirect economic losses caused by earthquake damage.
7.3.3 In the production buildings of aviation industry, the seismic defense category of the following buildings shall be classified as key defense category:
1 The building where the measurement reference of the ministerial level and above is located, and the building where the record and storage of the main products of aviation (e.g., airplanes, engines, etc.) or the storage of information of the key products are located.
2 on the development of the aviation industry has an important impact on the aircraft or system performance test facilities, key equipment where the building (such as large-scale wind tunnels and their test room, engine test bed and its power plant and test room, the whole electromagnetic compatibility test building).
3 Buildings that house important precision equipment rarely or only found in China.
4 The main power system building of medium and large enterprises.
7.3.4 In the aerospace industry production buildings, the seismic defense categories of the following buildings shall be classified as key defense categories:
1 Important aerospace industry scientific research buildings, production plants and test facilities, power system buildings.
2 Important demonstration, communication, measurement, training center buildings.
7.3.5 In the production buildings of the electronic information industry, the seismic protection category of the following buildings should be classified as a key protection category:
1 Large-scale color tubes, glass shell production plant and its power system.
2 large integrated circuits, flat-panel displays and other electronic production plants.
3 Important scientific research centers, testing centers, the main building of the test center.
7.3.6 Textile industry, chemical fiber production buildings, production buildings with chemical properties, the seismic protection category should be divided in accordance with Article 7.2.4 of this standard.
7.3.7 Large-scale pharmaceutical production buildings, with biological products nature of the plant and its control system, its seismic defense category should be divided according to this standard 6.0.9.
7.3.8 Processing and manufacturing industrial buildings, the production or use of highly toxic, flammable, explosive substances and fire hazards of the plant and its control system of the building, the seismic defense category should be divided into key defense category.
7.3.9 Large-scale machinery, ships, textiles, light industry, medicine and other industrial enterprises of the power system building should be categorized as key defense category.
7.3.10 machinery, shipbuilding industry production plant, electronics, textiles, light industry, medicine and other industrial production plant, it is appropriate to classify as a standard defense class.
8 Warehouse buildings
8.0.1 This chapter applies to industrial and civil warehouse buildings.
8.0.2 Warehouse buildings, according to the economic value of the stored goods and the secondary disaster caused by earthquake damage to the seismic defense category.
8.0.3 Warehouse buildings of seismic defenses should be consistent with the following provisions:
1 Storage of high and medium radioactive substances or highly toxic substances in the warehouse should not be lower than the key defense category, the storage of flammable, explosive substances and other hazardous materials with fire hazards warehouse should be classified as a key defense category.
2 general low value of stored goods, personnel activities, no secondary disasters, such as single-story warehouses can be categorized as moderate defense category.
The standard terminology
1 In order to facilitate the implementation of this standard (norms) provisions of the differentiation, the requirements of different degrees of strictness of the terminology is described as follows:
1) that is very strict, must not be done in this way the word: the positive word using the "must"; the negative word using the "strictly prohibited". The positive word is "must"; the negative word is "forbidden".
2) Words indicating that it is strict and should be done in all normal circumstances:
The positive word is "should"; the negative word is "should not" or "must not". ".
3) Words indicating that a little choice is allowed, and that this is the first thing to be done when conditions permit:
"It is desirable" is used for the positive word; "it is not desirable" is used for the negative word;
Words indicating that there is a choice, and that this can be done under certain conditions, "may" is used. under certain conditions, "may" is used.
2 standards (norms) in the specified should be implemented in accordance with other relevant standards, norms, written as: "should be consistent with the provisions of ......" or "should be implemented in accordance with ... ... ... implementation".
Construction Standards for Rural Ordinary Primary and Secondary Schools
Construction Standard 109-2008
Edited by: Ministry of Education of the People's Republic of China
Approved by: Ministry of Housing and Urban-Rural Development of the People's Republic of China
National Development and Reform Commission of the People's Republic of China
Date of Implementation: December 1, 2008