What size voltage regulator is needed for a 90KW machine, 100KVA? 150KVA How to calculate this !!!! urgently

KVA KVA is apparent power, which includes active and reactive power.

Kilowatt KW is active power.

Kilowatts (KW) = kilovolt-amperes (KVA) times power factor.

Active power P, reactive power Q, apparent power S has the following relationship P = S × cos Φ (Φ is the power factor)

The regulator labeled 150KVA is the apparent power, and you look at your machine power factor (cos Φ) is how much? (Generally in 80%-95%)

Specifically, we also need to consider the voltage regulator's transient load rate, generally require the rated only 80% of the long-term load,

Specific calculations: 90KW ÷ 80% ÷ power factor (cos Φ) = is the answer you want

Practical application of the 90kW load with a 150KVA is more appropriate.