On the hospital clean operating room air conditioning unit with electrode humidifier has a few questions, I hope to answer in detail, thank you!

1, first of all, the humidifier barrel is a consumable winter need to be replaced on a regular basis, the loss of serious and water quality, electrode scaling is too fast, can be used to soften the water.

2, the use of softened water humidifier scaling speed will be significantly reduced, but with the increase of sodium ions in the water, the conductivity of the water will increase to the point that the electrode in the steam drum will send out an arc light. The way to avoid the above situation is to use a mixture of softened water and tap water (mixed in a certain proportion) supply, not pure water, pure water is not conductive.

3, self-control system has a problem, the general process is: air conditioning fan off after the wind pressure switch detects the shutdown signal, and then transmitted to the self-control centralized controller, and then by the centralized controller output shutdown instructions to the humidifier.