I. Basis for Preparation
1. "The Law of the People's Republic of China on Work Safety"
2. "The Law of the People's Republic of China on Emergency Response"
3. "Guidelines for Preparation of Emergency Response Plans for Work Safety Incidents in Production and Operation Units"
4. "Measures for the Administration of Emergency Response Plans for Work Safety Incidents"
5, SINOPEC Emergency Response Plan
6. Emergency Response Plan of Puguang Branch
7. Emergency Response Plan of Gas Extraction Plant
II. Preparation Instructions
The Central Control Room is responsible for the monitoring of the fire gas system and process parameters of the gas extraction plant, the diagnosis of the SCADA system, the corrosion monitoring system, the monitoring, the safety control and security shutdowns, etc., with the focus on the monitoring of the valve room, the tunnel, Truss safety operation, the occurrence of dangerous situations timely report, while reaching the shutdown conditions, the implementation of emergency shutdown.
3. Introduction of Central Control Room
1. Introduction of Functions
The Central Control Room mainly completes the data collection, monitoring and safety protection functions of 16 gas gathering stations and 30 valve chambers in the whole pipeline network of Puguang main body, 18 valve chambers in 7 gas gathering stations of Dawan block, 1 gas gathering terminal and 1 sewage station of Zhaojiaba, and it is also used as the data center of the whole system to send data to the dispatching office of the gas production plant through OPC server. The server provides real-time production data to the dispatching office of the gas production plant and Dazhou base. In the central control room, there are two duty rooms, a communication cabinet room and a printer room with the purification plant, a power supply room with the gathering and transmission head station, and an operation hall with the purification plant and gathering and transmission head station. The central control room is equipped with SCADA, CCTV, voice softswitch, industrial Ethernet, office network, dispatching telephone, PCM, etc. It is capable of realizing the data collection, processing and archiving of the whole gas field, the dynamic display of the process flow, the diagnosis of the SCADA system, the monitoring of the corrosion monitoring system, the display of the alarms, the management of the alarms as well as the query and printing of the events, as well as the pivotal point for the monitoring and control, which can be realized through the operators' It can execute all levels of shutdown commands for each gas gathering station and the whole gas field through the operator's workstation and ESD hand manipulation station, and has powerful emergency shutdown functions.
2. Logical Shutdown of Putian Gathering and Transmission System
2.1 Introduction of Logical Shutdown
The central control room of gathering and transmission mainly accomplishes data acquisition, monitoring and safety protection functions for 23 gathering stations (16 in Puguang gas gathering area and 7 in Dawan gas gathering area), 1 terminus, 1 sewage treatment station in Zhaojiaba, as well as 48 line cut-off valve chambers (30 in Puguang gas gathering area and 18 in Dawan gas gathering area) in the whole gas pipeline network. It also serves as the monitoring and control center, dispatching command center and data center of the whole system, adopting the management system of centralized management and decentralized control. The emergency shutdown of Putian gathering and transmission section **** is divided into four levels of shutdown.
30 line cut-off valve room, three line cut-off valve room has five seats respectively: 1 #, 2 #, 3 #, 4 #, 5 #; double line cut-off valve room has four seats respectively: 6 #, 7 #, 8 #, 9 #; single line cut-off valve room has 21 seats respectively: 10 #, 11 #, 12 #, 13 #, 14 #, 15 #, 16 #, 17 #, 18 #, 20 #, 21 #, 22 #, 23 #, 24 #. 22#, 23#, 24#, 25#, 26#, 27#, 28#, 29#, 30#, 31#.
All 18 line chambers in the Dawan gas production area are single line chambers.
2.2 Overview of the four levels of shutdown in Putian
2.2.1 The first level of shutdown
The first level of shutdown is the shutdown of the whole gas field to stop production and keep pressure, and this level of shutdown is divided into two kinds of automatic interlocking shutdown and human-triggered shutdown.
①Reasons for automatic interlocking shutdown:
☆ Pressure preservation shutdown at the gas gathering station;
☆ Pressure relief shutdown at the gas gathering station;
☆ First-stage shutdown at the first station;
☆ First-stage shutdown at the purification plant;
Results of automatic interlocking shutdown:
Alarms:
Alarms: alarms for all-fields shutdown go to the purification plant;
All fields shutdown alarms go to the first station;
An alarm for ESD shutdown goes to the first station; ESD alarms go to the first station. Alarm to go to the first station; ESD-1 level start PA/GA; ESD-1 level hand-operated station indicator; hand-operated station buzzer alarm;
Shutdown section:
☆ Gathering station pressure preservation shutdown;
☆ P101 Gathering station pressure preservation shutdown;
☆ P101 Gathering station pressure preservation shutdown;
☆ P102 Gathering station pressure preservation shutdown;
☆ P103 Gathering station pressure preservation shutdown;
☆ P104 Gathering station pressure preservation shutdown; P105 Gas gathering station pressure preservation shutdown; P106 Gas gathering station pressure preservation shutdown; P107 Gas gathering station pressure preservation shutdown; P201 Gas gathering station pressure preservation shutdown; P202 Gas gathering station pressure preservation shutdown; P203 Gas gathering station pressure preservation shutdown; P204 Gas gathering station pressure preservation shutdown; P301 Gas gathering station pressure preservation shutdown; P302 Gas gathering station pressure preservation shutdown; P303 Gas gathering station pressure preservation shutdown; P304 Gas gathering station pressure preservation shutdown; P304 Gas gathering station pressure preservation shutdown. shutdown; P305 gas gathering station pressure preservation shutdown; D401 gas gathering station ESD-3 level shutdown, D402 gas gathering station ESD-3 level shutdown; D403 gas gathering station ESD-3 level shutdown; D404 gas gathering station ESD-3 level shutdown; D405 gas gathering station ESD-3 level shutdown; D502 gas gathering station ESD-3 level shutdown; D503 gas gathering station ESD-3 level shutdown.
②Triggered shutdown
Shutdown part: control center ESD hand manipulation station full gas field ESD-1 level button;
Triggered shutdown need to be analyzed by the control room operation engineers for false alarms, after judging that if it is not a false alarm, engineers from the hand manipulation station triggered the full gas field shutdown or from the human-computer interface on the soft triggering of the full gas field shutdown, triggered by man-made shutdown with the gathering system level 1 The result of the manually triggered shutdown is consistent with the automatic interlock shutdown of the gathering system level.
2.2.2 Secondary shutdown
The secondary shutdown of the gathering and transmission system is a branch line shutdown, which needs to be triggered by human beings for the shutdown of the upstream station, its own valve chamber and the neighboring valve chambers caused by the gas leakage in the valve chamber or the fire.
2.2.3 Tertiary shutdown
Tertiary shutdown is the station pressure relief shutdown or pressure maintaining shutdown, pressure relief shutdown and pressure maintaining shutdown need to be triggered by human beings.
2.2.4 Four-stage shutdown
The four-stage shutdown is the station unit shutdown. For the gas gathering station is a single shutdown, the wellhead pressure is 30MPa or less than 6MPa automatically interlock the well safety valve shutdown and stop the well heating furnace, but also for human shutdown of a well. Split acid separator liquid level below 25% automatically interlocked shutdown liquid phase outlet ESDV valve, can also be artificial shutdown liquid phase outlet ESDV valve.
Four-stage shutdown is a single-line shutdown for the gas gathering terminal.
☆ A single line inlet pressure below 7.0MPa automatically interlocks to shut down the inlet ESDV valve of this line;
☆ The level of the production separator is below 25% automatically interlocks to shut down the liquid phase ESDV valve of the separator.
Four, the control room personnel
Control room staff of 77 people, 5 management engineers, 22 external manipulation, internal manipulation of 50 people, 5 sets of small shifts of 10 people per shift, the implementation of the site "five shifts, three times" work system. They are responsible for the daily production operation, equipment management and emergency disposal of the head station and Zhaojiaba sewage station. At the same time monitoring the gas collection station (unattended station), valve room, tunnel safety operation, in accordance with the instructions to perform shutdown.
V. Risk Analysis
The mixture of gas output from the stations, valve chambers and tunnels is flammable, explosive and poisonous, with high concentration of hydrogen sulfide, high pressure, complicated terrain, dense population, difficulty in evacuating residents, and prone to wide-ranging hazards and other dangers after leakage.
1, fire
Station, valve room, tunnel equipment, pipelines, valves, flanges, instrumentation joints, etc., due to corrosion and perforation, aging seals or poorly sealed, will cause natural gas leakage, such as ignition sources are prone to cause fire.
2, explosion
Station containers, valve rooms, tunnel pipelines, etc. due to severe corrosion resulting in insufficient pressure capacity or due to operational errors, safety valve failure, ice blockage caused by overpressure, combustible gas leakage and air mixed to form an explosive mixture of gases, and fire out of control triggered by an explosion.
3, hydrogen sulfide leakage
Station, valve room, tunnel equipment, pipelines, valves, flanges, instrumentation joints, etc. due to corrosion and perforation, aging seals or poorly closed, hydrogen sulfide gas leakage, the environmental concentration of hydrogen sulfide will reach a safe critical concentration (20ppm) or more, more than the danger of the critical concentration (100ppm), and even reach a higher concentration, if the site If the operating personnel and the surrounding environment of the personnel to take improper measures, easy to trigger poisoning, resulting in casualties.
4, the wellhead device out of control
Putian natural gas components containing hydrogen sulfide 15%, 9% carbon dioxide, under certain conditions, easy to cause hydrogen embrittlement damage to steel, especially high-strength alloy steel and sulfide corrosion, and accelerate the aging of non-metallic materials, resulting in the destruction of the wellhead device, easy to cause the wellhead device out of control.
5, electrical fires and electrocution
Transmission and distribution lines of the power supply system, power distribution devices, various types of pumps and motors, lighting circuits and other electrical equipment and facilities, etc., the voltage is more than the safe voltage, if the grounding or zero protection device does not meet the requirements, insulation damage or aging, due to malfunctioning, misuse, unauthorized operation, and other reasons, triggered by electrical fires. Personnel touching the electrified body, will cause electric shock.
6, other dangers
On-site production operations, the staff there is a risk of mechanical injury such as bumping; hot weather work there is a risk of heatstroke; outdoor work there is a risk of snakebite, and so on.
Six, emergency disposal procedures classification
(a) pipeline
1, valve chamber hydrogen sulfide leakage (20-100PPM)
2, valve chamber hydrogen sulfide leakage (to achieve the conditions of the second level of shutdown)
3, the valve chamber fire and explosion
4, tunnel hydrogen sulfide leakage (20-100PPM)
5、Tunnel hydrogen sulfide leakage (reaching secondary shutdown conditions)
6、Pipeline hydrogen sulfide leakage
7、Pipeline (tunnels, through the span) fire and explosion
(B) manned gas gathering station
1、Hydrogen sulfide gas leakage (20-100PPM), abnormal discovery, emergency monitoring and command operation
2、Hydrogen sulfide gas leakage (reaching secondary shutdown conditions)
3, fire and explosion at gathering station
4, uncontrolled blowout at gathering station
(C) Unattended station
1, hydrogen sulfide gas leakage (20-100PPM)
2, hydrogen sulfide gas leakage (reaching secondary shutdown conditions)
3, fuel gas in heating furnace area Leakage
4. Gathering station fire and explosion
5. Gathering station electrical fire
6. Gathering station well blowout out of control
(d) Gathering station (see emergency disposal procedures for the main station)
(e) Wastewater treatment station (see emergency disposal procedures for the treatment station)
1. Valve chamber hydrogen sulfide leakage (20-100 ppm concentration) Emergency disposal procedures
Steps
Disposal
Responsible person
1Abnormal discovery
Human-machine interface of the central control room shows that the concentration of hydrogen sulfide in the X-valve chamber is 20-100 ppm, and the blower is started.
Position personnel
2 Reporting Confirmation
(1) Reporting: Position personnel A immediately reports to the plant dispatching room the time, location, and alarm concentration of the discovered alarm.
(2) Acknowledgement: Post person B immediately notifies the dispatching office of the gas production area through the walkie-talkie and rushes to the X-valve room for acknowledgement.
(3) Monitoring: Pay close attention to the change of concentration in the X valve room.
Posts A and B
3 Emergency Disposal
Confirmed by the on-site line patrol personnel, the leakage site can not be controlled, reported to the plant dispatch, according to the instructions of the central control room personnel to perform the second level of the gas field shutdown.
Shutdown: post personnel A to execute the corresponding logical shutdown. Shutdown Confirmation: Post person B confirms the shutdown situation and pays close attention to the pressure of the leaking pipeline. Monitoring: post person A monitors the well shutdown situation at the gas gathering station, the torch burning situation at the venting place, notification: post person B notifies the purification plant internal operation of the shutdown situation.
Posts A and B
4 Emergency report
Report to station manager: This is the central control room, according to the instruction of the plant regulator, the shutdown of valve room X is now executed, please instruct. Report to the plant regulator: I am the center control room, according to the instruction of the plant regulator, the shutdown of valve room X is now executed, please instruct.
Duty Engineer
5 Emergency Termination
(1) The central control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Superior personnel
Duty engineer
2. Valve room hydrogen sulfide leakage (ESD-2 shutdown conditions) emergency disposal procedures
Steps
Disposal
Responsible person
1 anomaly discovery
In the central control room man-machine interface displays the concentration of hydrogen sulfide in the X-valve room, the concentration of combustible gases, the concentration of hydrogen sulfide and combustible gases. ESD-2 level shutdown conditions are reached and the fan starts.
Post Personnel
2 Acknowledgement of Alarm
Post Personnel A Fire Gas System confirms that the alarm for the situation in valve room X is true and meets the logical shutdown conditions.
Post Personnel A
3 Emergency Disposal
Principle of Disposal: Dispose first, report later.
(1) shutdown: post person A performs the corresponding logical shutdown;
(2) shutdown confirmation: post person B confirms the shutdown and pays close attention to the pressure of the leaking pipeline.
(3) Inform: post person A informs the gas production area dispatching office of the leak and the shutdown measures taken.
(4) Monitor: post person B monitors the situation of well shutdown at the gas gathering station and the torch burning situation at the venting place.
(5) Notification: post person A notifies the purification plant internal operation of the shutdown.
Position personnel A and B
4 Emergency report
(1)Report to the plant regulator: This is the central control room, what time and what minute, a large amount of hydrogen sulfide leakage occurred in the X valve room, the concentration of the man-machine interface is ×××× ppm, and the shutdown of the X valve room has now been executed, and at the same time inform the gas extraction area, please instruct.
(2) The central control room reports to the station manager: This is the central control room, what time and minute, a large amount of hydrogen sulfide leakage occurred in the X# valve room, the concentration of the man-machine interface is ××××ppm, and now we have executed the shutdown of the X valve room, and at the same time, we have informed the gas production area, please instruct me.
Duty Engineer
5 Emergency Termination
(1) The central control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Superior personnel
Duty Engineer
Note: ESD-2 shutdown conditions: valve room hydrogen sulfide, combustible probes at the same time high high alarm reached or greater than 3.
3. valve room fire and explosion emergency disposal procedures
Steps
Disposal
Responsible
1 abnormal discovery
Control room HMI displays the X valve room temperature and smoke sensing detectors at the same time high alarm.
Position personnel
2 Confirmation of the alarm
(1) Confirmation: position personnel A confirms that the alarm of the temperature and smoke detectors in the X valve room is true.
(2) Alarm: post person B calls 4736119 to report the alarm.
Posts A and B
3 Emergency Disposal
(1) Shutdown: Post A performs the corresponding logical shutdown;
(2) Shutdown Confirmation: Post B confirms the shutdown and pays close attention to the pressure of the leaking pipeline.
(3) Inform: post person A informs the dispatching office of the gas production area that the X valve room is on fire and explodes, and the logical shutdown has been executed.
(4) Monitor: post person B monitors the well shutdown situation at the gas gathering station and the torch burning situation at the venting place,
(5) Inform: post person A informs the purification plant internal operation about the shutdown situation.
Posts A and B
4 Emergency Report
(1) Report to the plant transfer: I am the central control room, what time and what minute, the X valve room fire and explosion, the man-machine interface temperature and smoke detectors at the same time high alarm, has now executed the shutdown of the X valve room, and at the same time to inform the Puguang gas extraction area, please instruct.
(2) the central control room to the station manager: I am the central control room, what time a few minutes, X # valve room fire and explosion, man-machine interface temperature and smoke detectors at the same time high alarm, now the implementation of the X valve room shutdown, at the same time to inform the Puguang gas extraction area, please instruct.
Duty Engineer
5 Emergency Termination
(1) The center control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Supervisors
Duty Engineer
4. Emergency Disposal Procedures for Hydrogen Sulfide Leakage in Tunnel (Concentration 20-100 ppm)
Steps
Disposal
Responsible Person
1 Abnormality Discovery
Human-machine interface of the control room displays the concentration of hydrogen sulfide in X tunnel as 20-100 ppm. 100PPm.
Position Personnel
2 Reporting Confirmation
(1) Reporting: Post Personnel A immediately reports the time, location, and alarm concentration of the alarm discovery to the plant dispatching office.
(2) Acknowledgement: post person B immediately notifies the dispatching office of the gas extraction area through the walkie-talkie and rushes to the X tunnel for acknowledgement.
(3) Monitoring: pay close attention to the change of concentration in X tunnel.
Position personnel A and B
3 Emergency Disposal
Confirmed by the on-site line patrol personnel, the leakage site can not be controlled, reported to the plant dispatch, according to the instructions of the central control room personnel to perform the gas field secondary shutdown.
(1) shutdown: post personnel A to execute the corresponding logical shutdown.
Confirmation of shutdown: post person B confirms the shutdown and pays close attention to the pressure of the leaking pipeline.
(3) Monitoring: post person A monitors the well shutdown situation at the gas gathering station and the torch burning situation at the venting place,
(4) Notification: post person B notifies the purification plant internal operation of the shutdown situation.
Position Personnel A and B
4 Emergency Report
(1) Report to the Station Manager: This is the Central Control Room, according to the instruction of the plant regulator, the shutdown of Tunnel X has now been executed, please instruct.
(2) Report to the plant regulator: This is the center control room, according to the instruction of the plant regulator, X tunnel shutdown is now executed, please instruct.
Duty Engineer
5 Emergency Termination
(1) The central control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency response.
Supervisors
Duty Engineer
5. Emergency Response Procedures for Tunnel Hydrogen Sulfide Leakage (ESD-2 Shutdown Condition Reached)
Steps
Disposal
Responsible Person
1 Abnormality Discovery
Human-machine interface of the control room displays the hydrogen sulfide concentration in the tunnel X, the concentration of the combustible gases. ESD-2 level shutdown conditions are reached.
Post Personnel
2 Acknowledgement of Alarm
Post Personnel A Fire Gas System confirms that the alarm for the X tunnel situation is true and meets the logical shutdown conditions.
Post Personnel A
3 Emergency Disposal
Principle of Disposal: Dispose first, report later.
(1) shutdown: post person A performs the corresponding logical shutdown;
(2) shutdown confirmation: post person B confirms the shutdown and pays close attention to the pressure of the leaking pipeline.
(3) Inform: post person A informs the gas production area dispatching office of the leak and the shutdown measures taken.
(4) Monitor: post person B monitors the situation of well shutdown at the gas gathering station and the torch burning situation at the venting place.
(5) notification: post person A notifies the purification plant internal operation of the shutdown situation.
Position personnel A and B
4 Emergency report
(1)Report to the plant regulator: This is the central control room, what time and what minute, a large amount of hydrogen sulfide leakage occurs in the X tunnel, the concentration of the man-machine interface is ×××× ppm, and the shutdown of the X tunnel has now been executed, and at the same time, the gas extraction area is informed, please instruct.
(2) The central control room reports to the station manager: This is the central control room, what time and what minute, a large amount of hydrogen sulfide leakage occurred in tunnel X, the concentration of HMI is ××××ppm, tunnel X has been shut down, and the gas extraction area has been informed at the same time, please instruct.
Duty Engineer
5 Emergency Termination
(1) The center control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Superior personnel
Duty Engineer
Note: 1, Puguang gas extraction area ESD-2 shutdown conditions:
(1), Huangjiayan Tunnel, hydrogen sulfide, combustible counterprobe at the same time high high alarm reached four.
(2), eye-beam, Liujiapo tunnel hydrogen sulfide, combustible counter-radiation probes at the same time high high alarm to reach or greater than three.
(3), Shuijingyan, Huangling tunnel irrelevant break logic.
2, Dawan gas production area 8 tunnel shutdown conditions are:
Tunnel hydrogen sulfide, combustible counter-projector probe at the same time high high alarm or greater than 2
6. pipeline hydrogen sulfide leakage emergency response procedures
Steps
Disposal
Responsible
1 anomaly discovery
Central Control Room received Pipeline hydrogen sulfide leakage alarm
Position personnel
2 Emergency disposal
(1) Shutdown: Post personnel A performs the corresponding pipeline logic shutdown.
(2) Shutdown confirmation: post personnel B confirm shutdown, pay close attention to the leakage pipeline pressure.
(3) Notification: Person A notifies the gas production area dispatching office that a leak has occurred and shutdown measures have been taken.
(4) Monitor: post person B monitors the situation of well shutdown at the gas gathering station and the torch burning situation at the venting place.
(5) Notification: post person A notifies the purification plant internal operation of the shutdown.
Position personnel A and B
4 Emergency report
(1) Report to the plant transfer: I am the central control room, what time and what minute, to receive ×××× pipeline occurred a large number of hydrogen sulfide leakage, is now the implementation of the ×××× pipeline section shutdown, and at the same time to inform the gas production area, please instruct.
(2) The central control room reported to the station manager: This is the central control room, what time is it? I have received a large amount of hydrogen sulfide leakage from ×××× pipeline, and now we have executed the shutdown of ×××× pipeline section, and at the same time, we have also informed the Puguang gas production area, please instruct me.
Duty Engineer
5 Emergency Termination
(1) The central control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Superior personnel
Duty Engineer
7. pipeline (tunnel, through the span) fire and explosion emergency response procedures
Steps
Disposal
Responsible
1 anomalous discovery
Control room received the pipeline (tunnel, through the span) fire and explosion of hydrogen sulfide.
Post personnel
2 emergency disposal
(1) shutdown: post personnel A immediately execute the corresponding pipeline logic shutdown.
(2) shutdown confirmation: post personnel B to confirm the shutdown, pay close attention to the leakage pipeline (tunnel, through the crossing) pressure.
(3) Inform: post person A informs the gas production area dispatching office that shutdown measures have been taken.
(4) Monitor: post person B monitors the well shutdown situation at the gas gathering station and the torch burning situation at the venting place.
(5) Notification: post person A notifies the purification plant internal operation of the shutdown situation.
Position personnel A and B
4 emergency report
(1) report to the plant transfer: I am the central control room, what time and what minute, received the ×××× pipeline (tunnel, through the span) fire and explosion, is now the implementation of the ×××× pipeline section shutdown, and at the same time to inform the gas production area, please instruct.
(2) center control room to report to the station manager: I am the center control room, what time a few minutes, received ×××× pipeline (tunnel, through the span) fire and explosion, has now been implemented ×××× pipeline section shutdown, at the same time, inform the Puguang gas extraction area, please instruct.
Duty Engineer
5 Emergency Termination
(1) The center control room receives the instruction from the superior and follows the unified command of the superior.
(2) The source of leakage has been effectively controlled, the environmental impact has been controlled, the injured personnel have been properly placed, the superior emergency instructions have been implemented, the superior officer or duty engineer announced the termination of emergency.
Supervisors
Duty Engineer
8. Emergency Disposal Procedures for Hydrogen Sulfide Leakage (Concentration of 20-100 ppm) in Gathering Station
Step by Step
Disposal
Responsible Person
1 Abnormality Discovery
Human-machine interface of the central control room shows that the concentration of hydrogen sulfide is 20-100 PPm.
Position Personnel
2 Emergency Reporting
The central control room immediately informs the gathering station, district dispatching room, and plant dispatching room of the time, location, bit number, and concentration of the hydrogen sulfide probe alarm.
Position Personnel A and B
Duty Engineer
3 Emergency Disposal
(1) Monitoring: personnel status, production and operation parameters, hydrogen sulfide concentration.
(2) Instruction operation: Perform the corresponding operation according to the requirements of the post personnel of the gas gathering station.
Position Personnel A and B
4 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
9. Emergency Disposal Procedures for Hydrogen Sulfide Leakage (Reaching ESD-2 Shutdown Condition) in the Gathering Station
Step by Step
Disposal
Responsible Person
1 Abnormality Discovery
Human-machine interface of the central control room indicates that the concentration of hydrogen sulfide has reached ESD-2 shutdown condition. condition.
Position Personnel
2 Emergency Reporting
The central control room immediately informs the gathering station, district dispatching room, and plant dispatching room of the time, location, bit number, and concentration of the hydrogen sulfide probe alarm.
Position Personnel A and B
Duty Engineer
3 Emergency Disposal
(1) Execution of Shutdown: The Central Control Room triggers the ESD-2 (Pressure Maintaining) Shutdown when the personnel of the gas gathering station do not have the condition to trigger the shutdown.
(2) Monitoring: personnel status, production operating parameters, hydrogen sulfide concentration.
(3) Command operation: Perform the corresponding operation according to the requirements of the post personnel of the gas gathering station.
Position Personnel A and B
4 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
ESD-2 shutdown conditions are:
10, the gathering station fire and explosion emergency disposal procedures
Steps
Disposal
Responsible Person
1 Abnormality Discovery
The man-machine interface in the central control room displays the flame detector of the process plant area Alarm.
Position personnel
2 Emergency report
Central control room immediately informs the gas gathering station, district dispatching room, plant dispatching room alarm time, bit number.
Position Personnel A and B
Duty Engineer
3 Emergency Disposal
(1) Execution Shutdown: The Central Control Room triggers the ESD-1 (Pressure Relief) Shutdown when the personnel of the gas gathering station do not have the condition to trigger the shutdown.
(2) Monitoring: personnel status, production operating parameters, hydrogen sulfide concentration.
(3) Command operation: Perform the corresponding operation according to the requirements of the post personnel of the gas gathering station.
Position Personnel A and B
4 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
11. Emergency Disposal Procedures for Uncontrolled Well Blowout in Gathering Station
Steps
Disposal
Responsible Person
1 Abnormal Discovery
(1) The HMI of the Central Control Room displays the large-scale alarm of the hydrogen sulfide probe in the wellhead area.
(2) Fire in the wellhead area of the center control room.
Post Personnel
2 Emergency Report
The center control room immediately informs the gas gathering station, district dispatching room, and plant dispatching room of the alarm occurrence time, location, bit number, and concentration.
Position Personnel A and B
Duty Engineer
3 Emergency Disposal
(1) Execute Shutdown: When the personnel at the gas gathering station do not have the conditions to trigger the shutdown the Central Control Room triggers the ESD-1 (Pressure Relief) shutdown, initiates the ESD-1 shutdown, and shuts off the downhole safety valve of the well.
(2) Monitoring: personnel status, production operating parameters, hydrogen sulfide concentration.
(3) Command operation: Perform the appropriate operation as requested by the gas gathering station post personnel.
Position Personnel A and B
4 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
12, unmanned gathering station hydrogen sulfide leakage (concentration 20-100 ppm) emergency procedures
Steps
Disposal
Responsible person
1 Abnormal discovery
Human-computer interface of the central control room displays that the concentration of hydrogen sulfide is 20-100 ppm. 100PPm.
Position Personnel
2 Emergency Report
(1) The center control room immediately informs the gathering station position personnel to confirm the site.
(2) At the same time, report the scene to the district dispatching room and plant dispatching room.
Position Personnel A and B
Duty Engineer
3 Emergency Disposal
(1) Monitor: personnel status, production operating parameters, hydrogen sulfide concentration.
(2) Instruction operation: Perform the corresponding operation according to the requirements of the post personnel of the gas gathering station.
Position Personnel A and B
4 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
13, unmanned gas gathering station hydrogen sulfide leakage (ESD-2 shutdown conditions) emergency response procedures
Steps
Disposition
Responsible person
1 Abnormal discovery
Human-computer interface of the central control room shows that the concentration of hydrogen sulfide has reached the ESD-2 shutdown conditions. 2 shutdown condition.
Position Personnel
2 Emergency Disposal
Execute Shutdown: Central Control Room triggers ESD-2 (Pressure Retention) shutdown.
Post Personnel A and B
3 Emergency Reporting
The central control room immediately informs the gas gathering station, the district dispatch office, and the plant dispatch office of the time, place, and location of the alarm, as well as the shutdown operation performed.
Position Personnel A and B
Engineer on Duty
4 Emergency Monitoring
(1) Monitoring: personnel status, production operating parameters, hydrogen sulfide concentration.
(2) Command operation: Perform the appropriate operation according to the requirements of the gathering station post personnel.
Position Personnel A and B
5 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer
ESD-2 shutdown conditions are:
14, unmanned gas gathering station heating furnace area combustible gas leakage emergency response procedures
Steps
Disposition
Responsible persons
1 Abnormal discovery
Human-computer interface of the central control room displays Combustible gas detector and toxic gas detector alarm in the heating furnace area.
Post Personnel
2 Emergency Disposal
Execution Shutdown: Central Control Room triggers ESD-2 (Pressure Retention) shutdown.
Post Personnel A and B
3 Emergency Reporting
The central control room immediately informs the gas gathering station, the district dispatch office, and the plant dispatch office of the time, place, and location of the alarm, as well as the shutdown operation performed.
Position Personnel A and B
Engineer on Duty
4 Emergency Monitoring
(1) Monitoring: personnel status, production operating parameters, hydrogen sulfide concentration.
(2) Command operation: Perform the appropriate operation according to the requirements of the gathering station post personnel.
Position Personnel A and B
5 Emergency Termination
The emergency response is completed at the scene, and the emergency response is terminated in the center control room.
Supervisors
Duty Engineer