The secondary water supply facilities referred to in these regulations, refers to the urban public **** water supply network from the location of the valve at the point of withdrawal to the user metered water meter before the general term of the facilities, including pumping stations, water tanks (pools), pumps, valves, electronic control devices, disinfection equipment, pressure water containers, water pipelines and other facilities. Article III of these regulations apply to the city's urban areas and urban public **** water supply network connected to the secondary water supply and its management activities. Article IV municipal urban water supply department is responsible for the supervision and management of secondary water supply.
City and district health authorities are responsible for secondary water supply health supervision and testing.
Development and reform, finance, housing, public security, planning, quality supervision, price and other relevant departments in accordance with their respective responsibilities to do a good job of secondary water supply management. Article secondary water supply should be safe and reliable, health and environmental protection, energy-saving technology and equipment, the implementation of intelligent management.
Encourage enterprises and research institutions to develop and produce energy-saving water, safety and efficiency, water purification of secondary water supply facilities. Article 6 Any unit or individual in violation of the provisions of these regulations have the right to complain and report.
City water supply, health and other competent departments should be announced to the community complaints, reporting telephone, timely handling of complaints, reports. Chapter II Construction Management Article VII of the urban water supply department based on the special planning of urban water supply, integrated urban public **** water supply network construction, according to law to determine the setup of secondary water supply facilities. Article VIII of the new construction, alteration, expansion of buildings, drinking water pressure requirements over the city's public **** water supply network pressure standards, can not meet the demand for water, the construction unit or the property owner shall be supporting the construction of secondary water supply facilities.
Secondary water supply project design, construction, supervision, should be undertaken by units with appropriate qualifications.
Secondary water supply facilities are ancillary construction projects, should be designed, constructed and delivered at the same time as the main project. Article IX design of secondary water supply facilities by the competent health department and water supply units involved in technical review. Article 10 The design and construction of secondary water supply facilities, shall implement the relevant national and provincial norms and standards, and meet the following requirements:
(a) water meter out of the house, a household meter, metering to the household;
(b) the volume of the water storage facilities, pressurization facilities, the caliber of the pipeline in accordance with the conditions of the connection with the urban public *** water supply pipeline network and the management requirements;
(c) water storage Facilities should be set up independently, drinking water, fire water shall not be shared water storage facilities;
(d) water storage facilities should be sealed, rodent-proof, dust-proof, leak-proof, corrosion-resistant;
(e) water-related materials should be consistent with the national and the province's quality standards and drinking water hygiene standards, and shall not be used in the state and the province expressly prohibited or eliminated pipe, fittings, equipment and other non- Environmentally friendly water storage facilities;
(F) water storage facilities and pumping stations shall not be within 2 meters around the sewage pipeline, within 10 meters of septic tanks, soakaway wells and other contaminated facilities, and shall not be piled up poisonous, hazardous and corrosive substances;
(VII) secondary water supply facilities should be set up around the necessary security facilities;
(VIII) Laws, statutes and regulations Provisions of other requirements. Article XI after the completion of secondary water supply facilities, the construction unit shall, in accordance with the relevant technical specifications, flushing, pressure testing, disinfection, etc., by the statutory qualification of the water quality testing organizations to test and issue "water quality test report. Article XII of secondary water supply facilities after completion, the construction unit shall organize acceptance. Acceptance, the competent health department and water supply units shall be involved.
Without acceptance or unqualified acceptance, shall not be connected to the secondary water supply facilities and urban public **** water supply network.
After the acceptance of secondary water supply facilities, the construction unit should be within three months of the project file information transferred to the urban and rural construction archives institutions and to the urban water supply department for the record.
The urban water supply department in charge of the existing secondary water supply facilities should be collected, prepared for storage, the relevant units and individuals should actively cooperate. Chapter III operation and maintenance management Article XIII encourage the transfer of secondary water supply facilities to the water supply unit management, the implementation of urban public **** water supply network integration, specialized operation and maintenance.
Secondary water supply facilities are not transferred to the water supply unit management, by the property owner or its entrusted units responsible for operation and maintenance.
The transfer of secondary water supply facilities by the municipal people's government to formulate. Article XIV of secondary water supply facilities operation and maintenance management unit shall establish and improve the operation and maintenance of secondary water supply facilities management work system, service norms and safe operation procedures, and comply with the following provisions:
(a) in the water use of water storage in the valley time;
(b) the pump unit operation noise shall not be higher than the national standards for environmental noise;
(c) the roof tanks and Exposed secondary water supply facilities should be in accordance with the norms and abnormal cold weather normal water supply requirements, to take anti-fouling, anti-corrosion, anti-freezing measures;
(d) timely repair, update corrosion, damage, aging secondary water supply facilities and components;
(e) the implementation of security precautions and emergency management of emergency response measures, the implementation of the closed management of secondary water supply facilities;
(F) the establishment of secondary water supply facilities operation and maintenance management files, the operation, troubleshooting, cleaning, disinfection, inspection, renewal and reconstruction of records filed one by one.