(2) Take 2.0 for offices and classrooms; Its corridors, stairs and hallways take 2.5;
(3) Take 2.5 for canteens and restaurants; Its corridors, stairs and hallways take 2.5;
(4) The average balcony is 2.5;
(5) The corridor/staircase/hall/balcony and corridor/platform in the high-rise residential group where people may be crowded shall be 3.5;
(6) Take 2.0~2.5 for the bathroom (according to the load specification); Take 4.0 for the bathroom with bathtub and bathroom;
(7) Take 2.0 for residential kitchens, 4.0 for small and medium-sized kitchens and 8.0 for large kitchens (overweight equipment shall be calculated separately);
(8) Multi-function halls and terraced classrooms have fixed seats, taking 3.0; 3.5 No fixed seat;
(9) Take 3.5 for shops, exhibition halls and recreation rooms; Its corridors, stairs and foyer take 3.5;
(10) Take 4.0 for large restaurants, banquet halls, bars, dance halls, gyms and stages;
(1 1) auditorium, theater, cinema, fixed-seat stands, public laundry room take 3.0;
(12) Take 4.0 for automobile passage and parking garage;
(13) fire truck passage: one-way slab 35.0; Two-way slab floor and beamless floor take 20.0;
Note: when the fire truck exceeds 300KN, it should be converted into equivalent uniform live load according to the principle of structural equivalence. Structural load input: uncovered two-way slab (slab span ≥2.7m): slab and secondary beam 28, main beam 20; Two-way slab with soil cover thickness ≥0.5m (slab span ≥2.7m): slab ≤28, and equivalent load calculation table of fire truck in Liangjian Hospital; The rest need to be calculated separately and reviewed by the professional person in charge.
(14) Take 5.0 for stacks and files;
(15) stack fetching of dense cabinets12.0;
(16) Take 7.5 for the laundry room of large hotels;
(17) Computer Lab Test 3.0; Large and medium-sized computer rooms should be ≥5.0, or according to the actual situation;
(18) Take 7.0 for elevator machine room and ventilation machine room; The fan platform shall be 6 (No.5 fan or below) or 8 (No.8 fan);
(19) Take 8.0 for refrigerating machine room, hotel storage room, linen room and public toilet (including packing partition);
(20) Take10.0 for water pump room, power distribution room, generator room, bank vault and bill warehouse;
(2 1) pipeline conversion layer 4.0;
(22) Take 5.0 when someone reaches the roof of the room in the elevator shaft.