What are the requirements for installing high-efficiency filters in operating rooms in the medical industry?

What are the requirements for installing high-efficiency filters in operating rooms in the medical industry?

The installation of high-efficiency filters in the operating rooms of Shenzhen Minghao Purification Medical Industry should meet the following requirements:

1. Before the installation of the high-efficiency filters, it is not allowed to tear or open the packaging bag or Packing film; the air filter should be stored strictly in the direction marked on the high-efficiency filter packaging box; during the transportation of the high-efficiency filter, it should be handled and placed gently to avoid severe vibration and collision.

2. The operating room high-efficiency air filter should be installed immediately after passing the visual inspection; when the corrugated plate combination filter is installed vertically, the corrugated plate must be perpendicular to the ground; The connection with the frame is strictly prohibited from leakage, deformation, damage and glue leakage. The frame for installing the high-efficiency filter should be flat and clean. The flatness deviation of the installation frame of each high-efficiency air filter and filter without partitions should not exceed 1 to 2 mm; after installation, the inner wall must be clean and free of floating dust, oil, and Rust and debris, etc.

3. The installation direction of the air filter must be correct. After installation, the surrounding area of ??the filter and the interface should be tight and leak-proof;

4. When the high-efficiency filter adopts mechanical seal, it should use air seal. Gasket sealing; the compression of the gasket should be even after installation, and scanning should be performed to detect leaks after installation.

Package adoption?