Ks is the need coefficient, which is the ratio of the active power (i.e., the calculated load of Pjs) required by the power-using equipment at maximum load to the capacity of the equipment, Pe
Pjs is the calculated load, which is calculated by the statistical calculation of the load
Pjs=Pe x Ks
Ijs is the calculated current, Ijs = Pjs / (1.732xUexCosφ), where Ue refers to the rated voltage, Ue = 380V (three-phase electricity)
Cosφ is the value of the power factor, the general value of this value can be based on the nature of the load, look up the table to find out, you can also refer to the nameplate of the equipment