Detecting the door work to display the actual body temperature detected, more than 37.3 ℃ that is the alarm.
Temperature sensing detector is by monitoring the detection of changes in ambient temperature to achieve fire prevention, the use of high-quality linear sensors, SMD SMD processing technology production, with high sensitivity, stable and reliable, low power consumption, beautiful and durable, easy to use and so on. Circuit and power can be self-test, can be simulated alarm test.
Temperature sensing detector is suitable for relative humidity is often greater than 95%, no smoke and fire, a large amount of dust, smoke and dust retention under normal circumstances, kitchen, boiler room, generator room, drying workshop, smoking room, other smoke sensing detectors should not be installed in the halls and public **** place.
Temperature sensor detector installation requirements:
1, the detector in the protection of cables, stacks and other similar protection object, should be used in contact with the arrangement; set up in a variety of belt conveyors, it is appropriate to set up in the device near the hot spot.
2, set up under the roof of the line temperature-sensitive fire detector, the distance to the roof should be 0.1 meters. The protective radius of the detector should be consistent with the point-type temperature-sensitive fire detector protection radius requirements; detector to the wall distance should be 1 ~ 1.5 meters.