800RT freezer with what size cooling tower

In our experience, generally speaking, 800RT host with 800 cubic meters of cooling tower is more appropriate, there is a certain margin. In fact, 800RT is 800 cold tons of meaning, the cooling capacity of about 2800KW, 2800KW is 2800KJ / S, converted into hours should be multiplied by 3600 seconds, 10080000KJ / h, the general temperature drop of the cooling tower of 5 degrees, according to Q = CMT can be calculated, the flow of the cooling tower m = 480 cubic meters. But this is not accurate, generally to enlarge 1.3 times, the cooling tower flow rate of 624 cubic meters per hour. So the general selection of 800 tons

Huizhou Snowman Cooling Equipment Co., Ltd, specializing in the production of closed cooling tower.