I know on the Internet that you are engaged in refrigeration design, so I want you to help me I need to match the refrigeration equipment, please help me Thank you!

Calculation of the cooling capacity of the wind condenser water condenser heat transfer area calculation method and compressor matching selection

1) wind condenser heat transfer area calculation method

Cooling capacity + compressor motor power/200~250 = condenser heat transfer surface For example: (3SS1-1500 compressor) CT = 40 ℃: CE = -25 ℃ compressor capacity = 12527W + compressor motor power 11250W = 23777/230 = air condenser heat transfer surface 12527W + compressor motor power 11250W = 23777/230 = wind condenser heat transfer area of 103m2

2) water condenser heat transfer area with the ratio of wind condenser = estimated 1 to 18 (103 / 18) = 6m2

The area of the evaporator according to the compressor refrigeration (evaporating temperature ℃ × Δt relative humidity of the Huojheng coefficient of the table).

3) Refrigeration capacity calculation: = temperature difference × weight / time × specific heat × equipment maintenance agency

Example: there is a quick-freezing storage

1) library temperature -35 ℃

2) quick-freezing volume of 1T / H

3) time 2 / H within

4) quick-frozen substances (fresh fish)

5) Ambient temperature 27 ℃

6) equipment maintenance organization insulation board Calculation: 62 ℃ × 1000/2/H × 0.82 × 1.23 = 31 266 kcal / n can check the compressor evaporating temperature CT = 40 CE-40 ℃ refrigeration capacity = 31 266 kcal / n

General cold storage chiller simple selection and calculation method

(a) Cold Storage Fan matching (per cubic meter load according to W0 = 75W/m3)

1. Cold storage refrigeration unit and chiller matching according to -10 ℃ evaporation temperature calculation.

2. If V (cold storage volume) ﹤30m3, the number of times of opening the door is more frequent cold storage, such as fresh meat storage, then the multiplication coefficient A = 1.2

3. If 30m3 ≦ V﹤100 m3, the number of times of opening the door is more frequent cold storage, such as fresh meat storage, then the multiplication coefficient A = 1.1

4. If V ≧ 100 m3, the number of times of opening the door is more frequent cold storage, such as fresh meat storage, then the multiplication coefficient A = 1.0

5. = 1.0

5. If a single cold storage, the multiplication factor B = 1.1, the final cold storage chiller selection according to W = A × B × W0 (W for the chiller load)

(B) freezer fan matching (per cubic meter load according to the W0 = 70W / m3)

1. Cold storage refrigeration unit and chiller matching according to the evaporation temperature of -23 ℃ calculation

2. If V (cold storage volume) ﹤30m3, open the door more frequently cold storage, such as fresh meat storage, then multiply the coefficient A=1.2

3. If 30m3≦V﹤100 m3, open the door more frequently cold storage, such as fresh meat storage, then multiply the coefficient A=1.1

4. If V≧100 m3, the number of times of the more frequent cold storage, such as fresh meat storage, then multiply the coefficient A=1.0

5. If a single cold storage, the multiplication factor B = 1.1, the final cold storage chiller selection according to W = A × B × W0 (W for the chiller load)