What is TS-5 intelligent digital display controller

I. Use

TS-5 intelligent digital display controller can be used with DDZ-II, Ⅲ type instruments, various resistance strain pressure sensor / transmitter, force / load cell and other electric unit combination instrumentation supporting the use of the instrument is simple to operate, easy to use, stable and reliable performance, with alarm function. Widely used in force, pressure, temperature, flow, level, length and other physical quantities of the display, control.

II. Main technical indicators

1. Installation form: the instrument is a panel meter, can be easily installed in the instrument panel

Opening size (mm): 151 +1 × 75 +1

2. Alarm form: upper and lower limits of the dual-point alarm, the alarm point position can be set arbitrarily in 150% of the range, with light-emitting diode display and relay contact switching output form of alarm signals. Alarm signal. (Contact capacity of 5A, 220V resistive load)

3. Input signals and display:

Input signals: 0 ~ 10mA, 4 ~ 20mA, 1 ~ 5V, 0 ~ 5V, mV signals.

The display is adjustable from 0 to 9999 decimal point position, and the display unit can be selected due to the measurement object.

4. Accuracy level: 0.2%.

5. Working environment: power supply for AC 220V ± 10%, 50Hz. Power consumption: 10W

Temperature 5 ℃ ~ 50 ℃, humidity 0 ~ 90% RH, no corrosive gas occasions.

6. The table provides DC power supply 12V or 24V for the sensor.

7. External dimensions (mm): 160 × 80 × 180

8. Weight: about 1.0 kg

III. Panel description

1. Display window: display the measured value or set parameters.

2. Setting key PAR: Used for setting parameters such as upper and lower limits.

3. Data shift key ÷: Press this key when setting parameters to change the current input digit.

4. Data Increase Key ù: Press this key in the measurement state, the display shows the upper limit value for about 5 seconds. Pressing this key in the setting and calibration state will increment the current blinking digit by 1.

5. Data reduction key ü: Press this key in the measurement state, the display shows the lower limit value for about 5 seconds. Pressing this key in the setting and calibration state decreases the number of the current blinking digit in units of 1.

6. Zero key ZERO: Store the current value as zero point in MCU, no loss when power off.

7. Upper and lower limit alarm indication: light-emitting diode display.