1 1.4.4 The setting of the fire control room shall meet the following requirements:
1 The fire resistance rating of the independently built fire control room shall not be lower than Grade II;
2 The fire control room attached to the building should be located on the first floor of the building near the external wall, or on the underground floor of the building, but it should be separated from other parts according to the provisions of Article 7.2.5 of this specification, and should be equipped with a direct outdoor safety exit;
3. It is forbidden to pass through the electrical lines and pipelines that have nothing to do with the fire control room;
4 It should not be set near the computer room with strong electromagnetic interference and other computer rooms that may affect the work of fire fighting equipment.