dr unit room 6.5m * width 5.8 m2 = 37m2, room area and width in line with national standards.
CT machine room in the minimum effective use of the area of 30m2, the minimum length of one side of the machine room is 4.5m. according to the above national standards.
The design of the machine room, its area of not less than 25 square meters, the height of not less than 3.5 meters, X-ray tube should be placed in the center of the room, at least 2 meters away from the wall, the room shall not be piled up unrelated equipment and furniture.
The effective area of use in the DSA room should first meet the actual use of demand, single tube head DSA room should be used in the effective area of not less than 20 square meters, the minimum length of a single side of the room is not less than 3.5 meters.
Two-pipe head DSA room should be effective use of an area of not less than 30 square meters, the minimum length of a single side in the room is not less than 4.5 meters.
2, DSA equipment room to meet the conditions of normal installation and use of equipment, equipment room minimum floor height should not be less than 2.5 meters.
DR room for medical buildings is very important for a department, its role is to first understand the patient's condition in detail in order to make a more accurate diagnosis and treatment plan, but also the use of machines to understand the process of treatment of the patient's condition whether there is a change.