Fire alarm controller in the fire control room layout requirements

Fire alarm controller in the fire control room should be arranged in accordance with the following requirements.

Operating distance

The operating distance in front of the equipment panel should be less than 1.5m when arranged in a single row.

Viewing distance

On the side where the staff on duty often work, the distance from the equipment panel to the wall should not be less than 3m.

Maintenance distance

The maintenance distance behind the equipment panel should not be less than lm.

Centralized setup

Fire fighting equipment should be set up centrally in the fire fighting control room which is shared with other weak electric systems in the building.