Clean operating room is composed of what is a self-contained functional area

Chapter I General Provisions

In order to meet the needs of the hospital clean operating room construction, to meet the requirements of the development of medical care and scientific and technological progress, and to improve the effectiveness of investment, the development of this construction standard.

The second construction standards for the use of the hospital's new or remodeled clean surgical department project and built in the non-clean surgical department (district) of the put clean operating room and its auxiliary rooms project. The use of ventilation and air conditioning of the general operating room (room) projects can refer to the implementation of

Article 3 of the construction of clean surgical department, must comply with national laws and regulations relating to economic construction and health, in line with the relevant hygienic standards and clean technology standards are now determined.

Article 4 The construction of the clean operation department should adhere to the principle that its comprehensive performance meets the standard, pay attention to the air purification treatment, strengthen the protection of the operation area, the construction of the quasi-practical, economic principles, avoid one-sided pursuit of performance.

Article 5 of the construction of clean surgical department, in addition to the implementation of the construction standards, should also comply with the current national standards, norms and regulations.

Chapter II scale and composition of the Department of clean surgery

Article VI of the hospital clean surgery by clean operating rooms and auxiliary rooms, can be built to all clean operating rooms as the center and including the necessary auxiliary rooms, self-contained functional areas; can also be built to part of the clean operating rooms as the center and including the necessary auxiliary rooms, and ordinary surgery coexist with the Department of the independent (room). Functional area.

Article VII of the clean surgical department of various types of clean rooms should be based on its air or static conditions of bacterial concentration and air cleanliness level according to Table 1 class.

The clean rooms of the clean operation department shall be classified according to their air state or static condition and air cleanliness level.

The clean rooms of the clean operation department shall be classified according to their air state or static condition and the clean room of the clean operation department shall be classified according to their air state or static condition and the clean room of the clean operation department shall be classified according to their air state or static condition and the clean room of the clean operation department.

Peripheral area 0.4/30min?Φ90 dishes (10/m3)

Operating area class 100,

Peripheral area class 1000

Clean auxiliary room

Local class 100 area 0.2/30min?Φ90 dishes (5/m3),

Peripheral area 0.4/30min?Φ90 dishes (10/m3),

Peripheral area 0.4/30min? 90 dishes (10/m3),

Class 1000

(local class 100)

II

Clean operating room

Operating area 0.75/30min?Φ90 dishes (25/m3),

Peripheral 1.5/30min?Φ90 dishes (50/m3)

Operating area class 1000,

Peripheral area class 10,000

Clean auxiliary rooms

1.5/30min?Φ90 dishes (50/m3)

Class 10,000

III

Clean operating rooms

Operating area 2/30min?Φ90 dishes (75 dishes/m3),

peripheral area 4/30min?Φ90 dishes (50 dishes/m3)

Operating area class 10000,

Peripheral area class 100000

Clean auxiliary room

4/30min?Φ90 dishes (50 dishes/m3)

Class 100000<

IV

Clean operation room

5/30min?Φ90 dishes (50/m3)

300000

Clean auxiliary room

Article VIII: The scope of surgeries applicable to different levels of clean operation rooms is as follows:

I. I. Class I special clean operation room: applicable to joint replacement surgery, organ transplant surgery and brain surgery. Surgery, organ transplantation surgery and brain surgery, cardiac surgery, gynecology and other aseptic surgery;

II, II standard clean operating room: for thoracic surgery, plastic surgery, urology; hepatobiliary and pancreatic surgery, orthopedic surgery, and egg retrieval and support surgery and a class of general surgery aseptic surgery;

III, III general clean operating room for general surgery (remove), obstetrics and gynecology and other surgery. Class III general clean operating room, applicable to general surgery (remove a class of surgery), obstetrics and gynecology and other surgery;

Four, IV quasi-clean operating room; for anal and intestinal surgery and contamination and other surgeries.

Article IX clean surgical auxiliary rooms should include clean auxiliary rooms and non-clean auxiliary rooms, the scope of application is as follows:

A Class I clean auxiliary rooms: for reproductive laboratories and other special laboratories needing aseptic operation of the room;

Two, Class II clean transfusion auxiliary rooms; for extracorporeal circulation perfusion preparation of the room;

Three, Class III clean auxiliary room; applicable to brush hands, surgical preparation, sterile dressings and instruments, disposable items and precision instrument storage rooms, nurses' stations and clean corridors;

Four, Class IV clean auxiliary room: applicable to the recovery room, clean corridors and other quasi-clean places;

Five, non-clean auxiliary room: applicable to the doctor's and nurses' lounges, on-duty room, anesthesia Office, frozen section room, dark room, teaching rooms and family waiting place, changing shoes, changing clothes, bathrooms and purification of air-conditioning and other equipment rooms.

Article X of the main technical indicators of various types of clean rooms must comply with the provisions of Table 2.

The main technical indicators table

Name

Minimum static pressure (Pa)

Ventilation

Number of times

(times/h)

Surgical giant surgical combined (or local 100 work area) work surface height cross-section of the average wind speed (m/s)

Temperature (℃)

Relative

Humidity

(%RH)

Minimum fresh air volume

Noise

Minimum illumination

To neighboring low-level cleanrooms

(m3h/person)

(times/h)

dB(A)

(lx)

Specially clean

Operating room

+8

/

0.25~0.30

22~25

40~60

60

6

≤52

350

Standard clean

Operating room

+ 8

30~36

/

22~25

40~60

60

6

≤50

350

General clean

Surgery room

+5

20~24

22~25

35~60

60

4

≤50

350

Quasi-clean

Operating room

+5

12~15

/

22~25

35~60

60

4

≤50

350

Extracorporeal Circulation Perfusion Preparation Room

+5

17~20

/

21~27

≤60

/

3

.

≤60

150

Sterile dressings,

Instruments, disposable

Sexual goods room

and TM

Technical confidentiality equipment storage space

+5

10~13

/

21~27

≤60

.

3

≤60

150

Nurse's Station

+5

10~13

/

21~27

≤60

60

3

≤60

150

Preparation room

(Sterilization)

+5

10~13

/

21~27

≤60

30

3

≤60

200

Pre-anesthesia room

-8 <

10~13

/

22~25

30~60

60

4

≤55

150

Brushroom

>0

10~13

/

. 21~27

≤65

/

3

≤55

150

Clean Corridor

0~+5

10~13

/

21~27

≤65

/

. 3

≤52

150

Dressing room

0~+5

8~10

/

21~27

30~60

/

3

≤60

200

Restoration

0

8~10

/

22~25

30~60

/

4

≤50

200

Clean corridors

0~+5

8~10

/

/

<

21~27

≤65

/

3

≤52

150

Note: ①Clean area should maintain a positive pressure of not less than 10Pa on the non-clean area connected with it, and the clean area should maintain a positive pressure of not less than 15Pa on the outdoor area or on the area directly connected with the outdoor area, and the difference of all the squeezes should not be more than 30Pa. Difference should not be greater than 30Pa.

② Brush room without doors or located in clean corridors, the minimum static pressure can be greater than zero.

③The number of air changes and cross-section of the average air velocity design value should be within the table.

4 winter temperature extremes can be taken not less than the lower limit value in the table, the summer can be taken not more than the upper limit value in the table.

⑤The rooms whose names are not listed in Table 2 can refer to the rooms with similar uses to determine their index values.

⑤The room which has special requirements for the items, values and accuracy of the technical indexes should be designed according to the actual requirements

Article 11: The number, size and air cleanliness level of the clean operation room in the clean operation department should be decided according to the nature, scale, level and financial resources of the hospital. For general hospitals, the need to build Class I clean operating room, the number of clean operating room should not exceed 15% of the total number of clean operating room, at least one; conditions may be set up according to the need for a negative pressure clean operating room. For specialized hospitals, special clean operating room should be based on the actual need to determine the number of construction.

Article XII of the Department of Clean Surgery in the clean operating room according to Table 3 is divided into four scales, various scales of clean operating room net area should not exceed the value of the provisions of Table 3, must be more than should have a specific technical description, and more than the area should not be greater than the maximum net area of Table 3 of 25%.

Clean operating room plan scale Table 3

Scale category

Net area expansion

Reference length x width m

Extra-large

40 ~ 45

7.5x5.7

Large

30 ~ 35

5.7x5.4

Medium

25~30

5.4x4.8

Small

20~25

4

Chapter III Architecture

Article 13 The location of the clean surgical procedures within the hospital shall be far away from the sources of high contamination, and located on the upwind side of the direction of the most winds of the city or region in which it is located; and when there are the most and close to the When there are the most and close to the most two prevailing wind direction, then the clean surgical department shall be located in all the wind direction has the smallest wind frequency of wind direction of the opposite side.

Article XIV of the Department of clean surgery should not be located in the first floor and the top floor, when set up in the equipment (may not include large refrigeration units) layer of the next layer, must take effective measures for waterproofing, vibration and sound insulation treatment.

Article XV of the clean area and non-clean area should be set up between the buffer room with an area of not less than 3m2, the cleanliness level should be high with the clean side of the same level, and should not be higher than 1000 levels. There shall be transfer windows for logistics. Clean area in different air cleanliness levels between areas should be set up partition door.

Article XVI of the internal layout of the Department of Clean Surgery and channel forms should be in line with the principle of short functional processes and clean and dirty clearly, generally can choose the end of the arrangement, the center of the arrangement, lateral arrangement or ring arrangement in a kind of arrangement. Dirt with in situ disinfection and packaging measures can be used in a single channel, otherwise can be used to separate the clean and dirty double channel; when the conditions of diversion, can be used in multiple channels; when there are corridors, corridors should be designed as a clean corridor.

Article XVII of the clean operating room net height of 2.8-3m.

Article XVIII of the human and material elevators should not be located in the clean area. Subject to the conditions must be located in the clean area, the exit must be set up in the buffer room.

Article 19 of the brush room should be decentralized, every 2-4 operating rooms should be set up a separate brush room. When the conditions are available, can also be located in a clean corridor theater hand.

Article 20 of the clean operating room floor should be used wear-resistant, corrosion-resistant, dust-free, easy to clean and prevent the generation of static electricity materials. In general, can be used to cast embedded copper terrazzo floor and paint, coil floor.

Article 21 of the clean surgical department of the wall should be used without dust, flat and easy to clean materials. Generally can be used as a whole or assembled wall panels, class IV (not included) clean room can be used large tiles or paint.

Article 22 of the clean operating room door net width should not be less than 1.4m, should be equipped with automatic delay closing device of electric suspension automatic sliding door.

Article 23 The clean operation room and I, II clean auxiliary rooms should not be equipped with external windows, III, IV clean auxiliary rooms can be equipped with double-closed external windows.

Chapter IV clean operating room basic equipment

Article 14 of the clean operating room and operating room layout and building installation

basic equipment (excluding special mobile medical instruments and equipment) configuration, should be in line with the requirements of Table 4

.

Basic equipment Table 4

Name of equipment

Minimum number of configurations

Shadowless lamps

Operating tables

Timers

Medical gas supply units

Anesthesia gas venting unit

Hands-free intercom telephones

Pharmaceutical cabinets (built-in)

Instrument Cabinet (Recessed)

Anesthesia Cabinet (Recessed)

Viewing Lamp

Record Board

Infusion Rails (Including 4 Hooks)

l Sets/Each Room

1 Set/Each Room

1 Unit/Each Room

1 Only/Per Room

2 Sets/Per Room

1 Set/Each Room

1 Part

1/per room

1/per room

1/per room

1/per room

3 joints/small per room, A joint/medium per room,

6 joints/large per room

1 piece per room

five sets/per room

Chapter V: Air Conditioning and Air Purification

Article 25 Clean surgical treasure should be separated from the auxiliary rooms opened through the purification of air-conditioning system; clean operating rooms should be used to clean the air-conditioning unit is set up independently, III, IV clean operating room allows 2-3 rooms to share a system should be used for self-circulation of the return air; fresh air can be used to centralize the air supply system; exhaust system should be set up independently.

Article 26 of the purified air conditioning system should be at least three air filtration. The first level of air filtration should be set up in the new air outlet, the second level should be set up in the positive pressure section of the system, the third level should be set up at the end of the air supply or its vicinity.

Article 27 of the quasi-clean operating room can be used with sub-high efficiency filters or high-efficiency filters purified fan coil unit or indoor cabinet type purified air-conditioning unit, shall not be used for ordinary fan coil unit or air conditioner.

Article 28 Class I, II, III clean operating rooms and Class I, II clean auxiliary rooms, shall not be set up indoor radiators, but can be used as a radiant heat plate heating on duty. Class IV clean operating room and see, Class IV clean auxiliary rooms, such as the need to set up radiators, should be used not easy to accumulate dust and easy to clean the type, and set up protective cover. Radiator heat medium should not be higher than 95 ℃ hot water.

Article 29 I, II, III clean operating room should be used in a localized centralized air supply, centralized arrangement of the air supply area that the size of the surgical area should be compatible with the level of the operating room, the I level is not less than 6.2 expansion (of which the head of the special no less than 1.4m2), IV level is not less than 4.6m2, III level is not less than 3.6m2. According to the need for clean auxiliary room can be equipped with local 100 level. According to the needs of clean auxiliary room can be set up in the local 100-class area.

Article 30 of the electrostatic air purification device shall not be used as a purification air-conditioning system for the final level of purification facilities, and shall not be used as a stand-alone unit located directly in the clean operating room and clean auxiliary rooms.

Chapter VI medical gas, water supply and drainage, power distribution

Article 31 The Department of clean surgery must be set up oxygen, compressed air and negative pressure to attract three kinds of gas and devices. Nitrous oxide (nitrous oxide that laughs), nitrogen, argon gas and exhaust gas recycling and emission devices when needed. Medical gas must have no less than three days of spare capacity. Clean operating room medical gas terminal must have a set of spare.

Article 32 of the water supply system within the clean operating department should have two imports, and there should be no hot and cold water system at the same time.

Article 33 of the water supplied to the clean surgical department must meet the drinking water standards; brushing water should be desirable to remove bacteria; hot water storage should be prevented from breeding bacteria measures.

Article 34 The clean surgical department should be equipped with direct fire hydrant water supply system and portable gas fire extinguishers. Clean surgical department need to set up automatic sprinkler system, the nozzle should not be located in the operating room. Smoke detectors should be provided in the clean operating room. Clean surgical department of the technical mezzanine should be set up at the same time the fire fighting facilities.

Article 35 of the Department of clean surgery must be set up to automatically switch the dual-channel power supply, from the building where the power distribution center dedicated line supply.

Article 36 The electricity used in the clean operation room shall be separated from the electricity used in the auxiliary room, and the trunk line of each operation room shall be laid separately.

Article 37 The total load of distribution of medical equipments and devices in the clean operation room should not be less than 8kVA in addition to meeting the design requirements

Article 37 The total load of distribution of medical equipments and devices in the clean operation room should not be less than 8kVA.