1, the purification of air conditioning mainly refers to ensure the cleanliness of the room, to prevent the outside of the polluted airflow into the room.
2, the main function is:
The main function in order to ensure the cleanliness of the room, to prevent the outside of the polluted airflow into the room. Make the indoor air to maintain a good environment. Can reduce or elevate the temperature, reduce or increase air humidity and moisture, reduce the content of particulate soot pollutants in the air.
Air purification features are used to provide a protective and comfortable environment for staff as well as products.
Air conditioning purification systems typically include air handling units, supply and return air ducts, duct accessories, and terminal filtration devices.
3, the main use of:
Mainly used in pharmaceutical, chemical, hospital operating rooms, negative pressure wards, animal rooms, medical equipment, food and beverage, sterile laboratory,
P-level experiments, GMP net aseptic operating room, negative pressure wards, laminar flow wards, GMP purification workshop, electronic clean room, beverage filling plant, QS food purification workshop,
Pure water purification system is mainly used to purify the air conditioning system. p>
Pure water filling workshop, constant temperature and humidity laboratory, dust removal workshop, self-flowing floor, LG coil floor, aseptic filling workshop, purification air-conditioning unit.
Expanded Information:
Purification of air conditioning precautions:
1, purification of air conditioning units and built-in parts of the internal surface should be selected to resist corrosion of disinfectant drugs materials or surface layer. The surface of the material should be smooth.
2, the internal structure should be easy to clean and can smoothly remove the cleaning waste water, not easy to accumulate dust and bacteria.
3, the surface cooler condensate outlet, should be able to automatically prevent suction and condensate can be discharged smoothly in negative pressure device.
In dehumidification conditions should be discharged in the system running 3MIN water. Condensate pipe can not be directly connected to the sewer.
4, before and after all levels of air filters should be set up before and after the differential pressure gauge, measurement of the receiver should be smooth, tightly installed.
5, should not be used drench air processor. When the surface cooler, through the coil where the cross-section of the air velocity should not be greater than 2M / S.
6, air conditioning unit in the humidifier should be used dry steam humidifier, in the humidification process should not be water droplets.
Humidification water quality should meet the health standards for drinking water. Humidifier material should be corrosion resistant, easy to clean and check.
7, humidification equipment and its air-conditioning equipment after the segment to have a sufficient distance between. Ⅰ ~ Ⅲ clean room purification air-conditioning system before the high-efficiency filter system air relative humidity should not be greater than 75%.
8, air conditioning unit box sealing should be reliable. When the unit to maintain a static pressure value of 1000PA, cleanliness equal to or higher than 1000 level of the system, the air leakage rate of the box should not be greater than 1%.
Cleanliness is lower than 1000 level of the system, the box leakage rate should not be greater than 2%.